6  Commissioning 
Issue 10/06 
 
MICROMASTER 440 
56 
Operating Instructions (Compact) 
6.4.18.3 Holding 
brake 
¾
 
Series / commissioning for hazardous loads  
−  lower the load to the floor 
−  when replacing the frequency inverter, prevent (inhibit) the frequency 
inverter from controlling the motor holding brake (MHB) 
−  secure the load or inhibit the motor holding brake control (so that the brake 
cannot be controlled) and then – and only then – carry-out quick 
commissioning / parameter download using the PC-based tool (e.g. 
STARTER, AOP) 
¾
 
Parameterize the weight equalization for hoisting gear applications 
−  magnetizing time P0346 greater than zero 
−  min. frequency P1080 should approximately correspond to the motor slip 
r0330 (P1080 ≈ r0330) 
−  adapt the voltage boost to the load 
a)  V/f (P1300 = 0 ...3):  P1310, P1311 
b)  SLVC (P1300 =20):  P1610, P1611 
¾
  It is not sufficient to just select the status signal r0052 bit 12 "motor holding 
brake active" in P0731 – P0733. In order to activate the motor holding brake, in 
addition, parameter P1215 must be set to 1. 
¾
  It is not permissible to use the motor holding brake as operating brake. The 
reason for this is that the brake is generally only dimensioned/designed for a 
limited number of emergency braking operations. 
¾
  The brake closing / opening times can be taken from the appropriate manual. 
The following typical values have been taken from Motor Catalog M11 
2003/2004, Page 2/51: 
Motor size 
Brake type 
Opening time [ms] 
Closing time [ms] 
63 2LM8 
005-1NAxx 25 
56 
71 2LM8 
005-2NAxx 25 
56 
80 2LM8 
010-3NAxx 26 
70 
90 2LM8 
020-4NAxx 37 
90 
100 2LM8 
040-5NAxx  43 
140 
112 2LM8 
060-6NAxx  60 
210 
132 2LM8 
100-7NAxx  50 
270 
160 2LM8 
260-8NAxx 165 
340 
180 2LM8 
315-0NAxx 152 
410 
200 
225 
2LM8 400-0NAxx 
230 
390 
 
 
Holding brake enable 
Enables/disables holding brake function (MHB). 
  0  Motor holding brake disabled 
  1  Motor holding brake enabled 
NOTE 
The following must apply when controlling the brake relay via a digital output: P0731 = 52.C 
(= 52.12) (refer to Section 6.4.4 "Digital outputs (DOUT)"). 