APC SY160K160H User Manual

Page of 36
Troubleshooting: UPS Alarms
24
Symmetra PX 160 kW 400 V Operation
990-3015-001
Redundant Intelligence Module 
Fault
The redundant intelligence module 
has failed and requires replacement.
Redundant Intelligence Module 
in Control
The main intelligence module has 
failed, the redundant intelligence 
module is functioning as the primary 
intelligence module.
Replacement Battery Needed
One or more battery units needs to 
be replaced.
Runtime Alarm
The predicted runtime is lower than 
the user-specified minimum runtime 
alarm threshold. At least one battery 
module has failed or the load has 
increased.
Option 1: Install additional battery 
modules.
Option 2: Replace failed battery modules.
Option 3: Reduce the load.
Option 4: Change the alarm limit.
Site Wiring Fault
There is a problem with the phase 
rotation or a phase is missing in the 
input voltage to the UPS.
Contact APC Customer Support.
Static Bypass Switch Module 
Fault
The static bypass switch module has 
failed and requires replacement.
Contact APC Customer Support.
Static Bypass Switch Module 
Removed
The system no longer detects a static 
bypass switch module.
Option 1: Ensure the static bypass switch 
module is installed properly.
Option 2: Replace the static bypass switch 
module.
System ID Card Fault
The system ID card has failed and 
requires replacement.
System ID Card Removed
The system no longer detects a 
system ID card.
Option 1: Ensure the system ID card is 
installed properly.
Option 2: Replace the system ID card.
System Level Fan Fault
The system level fan has failed and 
requires replacement.
Contact APC Customer Support.
System Power Supply Card 
Fault
The system power supply card has 
failed and requires replacement.
System Start-Up Configuration 
Fault
The system configuration download 
failed. Unable to determine the 
system voltage or frame size.
Check for other alarms and contact APC 
Customer Support.
XR Communication Card Fault The XR communication card has 
failed and requires replacement.
XR Communication Card 
Removed
The system no longer detects a XR 
communication card.
Option 1: Ensure card is installed 
properly.
Option 2: Replace the card.
Display Message
Meaning
Corrective Action