Symmetra PX 160 kW 400 V Operation
990-3015-001
PDU fault list
Display Message
Meaning
Corrective Action
Maintenance Bypass Alarm The system is in maintenance 
bypass: the Q2 switch is open 
and the Q3 switch is closed.
No corrective action necessary.
Output V <Ln-N>
Voltage Under Limit
Phase-to-neutral output voltage 
for phase <L-N> has dropped 
below the configured limit.
Evaluate the threshold setting. If necessary, 
adjust it for your situation.
Output V <Ln-N>
Voltage Over Limit
Phase-to-neutral output voltage 
for phase <L-N> exceeded the 
configured limit.
Evaluate the threshold setting. If necessary, 
adjust it for your situation.
Output I L<n>
Current Over Limit
Current of output phase <n> 
exceeded the configured limit.
Evaluate the threshold setting. If necessary, 
adjust it for your situation.
Output I L<n>
Current Under Limit
Current of output phase<n> 
dropped below the configured 
limit.
Evaluate the threshold setting. If necessary, 
adjust it for your situation.
Output FDev
Freq Out of Range
Frequency of the output current 
is above or below the range that 
is configured as acceptable.
Evaluate the threshold setting. If necessary, 
adjust it for your situation.
<User Contact Name>
Alarm Active
A user-configured contact 
connected to the system is 
reporting an alarm condition.
Determined why the alarm has occurred. This 
is a user-specific alarm setting.
No UPS Input
Breaker Q1 Open
The Q1 circuit breaker is open, 
and the UPS is disconnected 
from the input voltage.
Close the Q1 switch to re-connect the UPS to 
utility/mains power.
No Panel Feed
Breakers Q2 & Q3 Open
The Q2 & Q3 circuit breakers 
are open, and the system is not 
supporting connected 
equipment.
For safety reasons, ensure the switches were 
not closed for maintenance purposes. If not, 
close Q2 for UPS operation, and Q3 for 
maintenance bypass.
Atypical Bypass Mode
Alarm 
The system state as set by the 
Q1, Q2, & Q3 breakers is in a 
non-typical bypass mode.
Option 1: Resume normal UPS operation.
Option 2: Go to maintenance bypass.