APC SY160K160H User Manual

Page of 36
990-3015-001
Symmetra PX 160 kW 400 V Operation
25
Modular Distribution fault list
The display interface will identify the number of the power distribution module that has caused an 
alarm or warning. 
Display Message
Meaning
Corrective Action
High Module Current 
The high module current 
threshold has been exceeded.
Evaluate the threshold setting. If necessary, adjust 
it for your situation.
High Subfeed Current
The high subfeed current 
threshold has been exceeded.
Evaluate the threshold setting. If necessary, adjust 
it for your situation.
Low Module Current
The low module current 
threshold has been exceeded.
Evaluate the threshold setting. If necessary, adjust 
it for your situation.
Low Subfeed Current 
The low subfeed current 
threshold has been exceeded.
Evaluate the threshold setting. If necessary, adjust 
it for your situation.
Maximum Module Current
The maximum module current 
threshold has been exceeded.
Evaluate the threshold setting. If necessary, adjust 
it for your situation.
Maximum Subfeed Current
The maximum subfeed current 
threshold has been exceeded.
Evaluate the threshold setting. If necessary, adjust 
it for your situation.
Minimum Module Current
The minimum module current 
threshold has been exceeded.
Evaluate the threshold setting. If necessary, adjust 
it for your situation.
Minimum Subfeed Current
The minimum subfeed current 
threshold has been exceeded.
Evaluate the threshold setting. If necessary, adjust 
it for your situation.
Modular Distribution 
Communication
Communication has been lost 
with the modular distribution 
breakers.
Check the communication cables to ensure they 
are properly connected. Contact APC Customer 
Support.
Module Breaker Open
A modular circuit breaker is 
open.
Check the modular circuit breakers to see if one 
has overloaded. Replace if necessary.
Subfeed Breaker Open
A subfeed circuit breaker is 
open.
Check the subfeed circuit breakers to see if one 
has been over-loaded.