Siemens 6ED1050-1AA00-0BE8 User Manual

Page of 372
 
Programming LOGO! 
 
3.8 Configuring additional functions for LOGO! (0BA7 only) 
LOGO! 
Manual, 04/2011, A5E03556174-01 
121
 
3.8.3 
Configuring the Data Log 
You can configure the Data Log block only from LOGO!Soft Comfort. 
You can configure a maximum of one Data Log for your circuit program using LOGO!Soft 
Comfort. The Data Log is used to record process measurement variables of the selected 
function blocks. For a detailed description of configuration of the Data Log function in 
LOGO!Soft Comfort, refer to the online help for LOGO!Soft Comfort V7.0. 
If your circuit program in LOGO! contains the Data Log block, you can configure elements 
connected to the block. For more information of configuration of Data Log elements from 
LOGO! 0BA7, refer to the topic Data Log (0BA7 only) (Page 285). 
3.8.4 
Viewing network inputs/outputs 
LOGO!Soft Comfort provides you with the following connectors representing network 
input/output blocks: 
●  Network digital inputs (identified with an NI in LOGO!) 
●  Network analog inputs (identified with an NAI in LOGO!) 
●  Network digital outputs (identified with an NQ in LOGO!) 
●  Network analog outputs (identified with an NAQ in LOGO!) 
Network digital or analog inputs can connect with the inputs of function blocks. Network 
digital or analog outputs can connect with the outputs of function blocks. 
If your circuit program contains a network digital/analog input, LOGO! can read a 
digital/analog value from another circuit program in a networked device. If your circuit 
program contains a network digital/analog output, LOGO! can write its digital/analog output 
value to another networked 0BA7 device in slave mode.  
 
 
Note 
You can only configure these network connectors for your circuit program from LOGO!Soft 
Comfort. If your circuit program in LOGO! contains a network connector, you can not make 
any edits to the circuit program from the LOGO! onboard display.