Adding or Removing Cabinet Hardware 
6-107
Add a Switch Node Carrier (Standard Reliability) 
6
Resolve Alarms and Enable Alarm Origination
1. Examine the alarm log. Resolve any alarms using 
DEFINITY Enterprise 
Communications Server Release 8 Maintenance for R8r.
2. If the 
Alarm Origination Activated f
ield administration that you 
previously noted is already set to y, be sure to enable Alarm Origination. 
Otherwise you do not need to enable Alarm Origination (proceed to the 
next section).
3. Type change system-parameters maintenance and press 
Enter
.
The name of the 
Alarm Origination Activated
 field was changed to 
Alarm Origination to OSS Numbers
 to support more than 1 OSS.
4. Type first-only in this field to enable Alarm Origination (to the first OSS, 
which should be INADS). 
Be sure to type y in both 
Cleared Alarm Notification
 and 
Restart 
Notification
 fields. Press 
Enter
.
5. Type save translation disk and press 
Enter
.
If you have lost the previous administration of the 
Alarm Origination
 
field, you may register the system again with the INADS Database 
Administrator at the TSC. The INADS Administrator enables Alarm 
Origination as part of the registration process.
!
WARNING:
If you do not enable Alarm Origination when the customer has 
purchased a services contract, the switch will not report any alarm to 
the TSC automatically, causing the TSC to be unable to fulfill the 
services contract.