DEFINITY Enterprise Communications Server Release 6
Installation and Test for Compact Modular Cabinets  
555-230-128  
Issue 3
May 1998
Installation Completion and Cable Pinouts 
Page 2-2
Perform System Administration 
2
Enable Alarm Origination to INADS
No External Modem Installed (or No Alarm Origination to INADS)
1. Enter change system-parameters maintenance and press 
Enter
2. Enter n in the 
Alarm Origination Activated to OSS Numbers 
field and press 
Enter.
 
3. For some software releases, enable 
Cleared Alarm Notification
 and 
Restart Notification
 before the submitting the form.
External Modem Installed
1. Enter change system-parameters maintenance and press 
Enter
2. Enter y in the 
Alarm Origination Activated to OSS Numbers 
field and press 
Enter.
 
3. For some software releases, enable 
Cleared Alarm Notification
 and 
Restart Notification
 before the submitting the form.
4. Be sure the system is part of the INADS database by calling the INADS 
Database Administrator at the Technical Service Center (TSC). Verify that 
INADS can dial into the system and that the system can dial out to INADS. 
As part of the system registration process, the INADS Database 
Administrator enables Alarm Origination and customer options.
NOTE:
When calling from a remote modem, you may need to disable error 
correction to allow the modems to connect successfully. For 
example, the AT&T Paradyne KeepInTouch
®
 modem may require the 
“AT\n0” command.
5. Log off and log back in.
Place a Test Call
1. From any telephone connected to a digital line circuit pack, call any 
nearby telephone connected to an analog line circuit pack.
2. Verify that the dial tone, ringing pattern, and talk path are acceptable.
3. Place a call through the Central Office (outside call) to any nearby 
telephone. Verify that the dial tone, ringing pattern, and talk path are 
acceptable.