Installation Completion and Cable Pinouts 
Page 2-3
Set Neon Voltage — Ring Ping 
2
Set Neon Voltage 
— 
Ring Ping
NOTE:
If the ringing option is set to 50 Hz, neon voltage is not available. If 25 Hz is selected, 
the maximum voltage is 120 volts. Refer to 
.
NOTE:
Set the control to OFF if there are no 
neon
 message waiting lamps or if LED message 
lamps are used. See 
Figure 2-1
.
Figure 2-1.
Setting the Neon Voltage
1. Call a telephone with a neon message indicator and leave a message.
2. Check for “ring ping” (single ring pulse) each time the lamp flashes 
(approximately every 3 seconds).
3. Adjust the control clockwise in small increments until the ring ping stops. 
Be sure that the message lamp still lights when the adjustment is finished.