Toshiba HCV-1JBU Instruction Manual

Page of 30
 
Page 10 
 
INSTALLATION 
 
 
 
AMBIENT CONDITIONS 
 
Do not install this 
equipment in areas where 
unusual service conditions 
exist. Using this equipment 
in other than usual service 
conditions can result in 
equipment failure. 
 
Toshiba  HCV-1JBU  and  HCV-1KAU  contactors 
are intended for use in usual service conditions 
as defined in NEMA ICS 1. The temperature of 
the  cooling  air  (ambient  air  temperature) 
surrounding the contactor should be between the 
limits  of  -5°C  (23°F)  and  +40°C  (104°F).  The 
altitude  of  the  equipment  installation  should  not 
exceed 3300-ft (1000 m). 
 
In  particular,  avoid  the  following  installation 
conditions: 
 
-
  Excessive dust 
-
  Corrosive gases 
-
  Extreme variations in temperature 
-
  Very high or low humidity 
-
  Vibrations 
-
  Inclined locations 
 
If there is a chance that condensation can occur 
at the installation location, a space heater should 
be installed inside the contactor enclosure. 
 
NOTE:   Temperature,  altitude  or  other 
conditions  outside  of  the  usual  limits 
may require derating or other special 
equipment.  Contact  your  nearest 
Toshiba  representative  for  additional 
information. 
 
 
 
 
MOUNTING THE CONTACTOR 
 
The  contactor  is  designed  to  mount  to  a  flat, 
vertical surface.  If there are any noticeable gaps 
between the contactor and the mounting surface, 
fill them in using flat washers as spacers. 
 
Fasten  the  contactor  using  four  (4)  M8  hex 
head  bolts.    The  tightening  torque  should  be 
120-150  kgf-cm  (9-11  ft-lb).    See  Table  1  for 
tightening torque specifications. 
 
 
MAIN CIRCUIT CABLE CONNECTIONS 
 
Route  cables  that  connect  to  the  contactor  to 
avoid interference with sharp edges and moving 
parts.  Observe minimum bending radius for the 
type of cable used. 
 
Power cables should be braced and/or laced to 
withstand  short-circuit  forces  wherever  such 
cables are unsupported.  Power cables should 
be  adequately  sized  to  carry  the  maximum 
continuous  current  in  accordance  with  NEC 
requirements  and  should  have  an  adequate 
voltage rating.  Cables should be dressed and 
terminated  as  appropriate  to  the  voltage  class 
and cable manufacturer’s recommendations.  
 
Fasten the cables to the main circuit terminals.  
Use  35  mm  Class  8.8  M10  or  M12  hex  head 
bolts, 2 flat washers, a lock washer and a nut.  
While securely preventing the nut from rotating 
with  a  wrench,  torque  the  bolt  to  250-315  kgf-
cm (18-23 ft-lb) for M10 bolts or 450-565 kgf-cm 
(32-41 ft-lb) for M12 bolts. 
 