INSTALLATION 
 
Page 11 
 
 
 
Use two wrenches to 
torque the connection to 
prevent applying excessive 
force to the terminal, which 
can damage the frame. 
 
GROUND CONNECTIONS 
 
The contactor must be grounded in accordance 
with the requirements of the National Electrical 
Code, Article 250 or applicable local standards. 
 
Proper grounding 
connections must be made 
to the contactor before 
incoming power is applied. 
 
It  is  very  important  that  the  contactor  be 
adequately  grounded  to  protect  the  operator 
from injury in the event of short circuits or other 
abnormal  occurrences  and  to  ensure  that  the 
metal  parts  of  the  equipment,  other  than  live 
parts, remain at ground potential. 
 
The ground terminal is located on the left side 
of the contactor as shown in Figure 6.  To make 
the  ground  connection,  first  remove  the 
fastening  M8  hex  head  bolt  and  crimp-on 
terminal (provided with the contactor) and crimp 
the terminal to the end of the ground wire. 
 
 
Figure 6 - Ground Connection Location 
 
 
 
The  ground  wire  should  be  8  AWG  or  larger.  
Then reattach the terminal using the same bolt 
previously  removed  and  torque  to  9-11  ft-lb 
(120-150 kgf-cm). 
 
 
CONTROL CIRCUIT CONNECTIONS 
 
Hazardous Voltage. Turn off 
and lock out all primary and 
control circuit power 
sources prior to performing 
this pre-energization check.  
Applying the specified 
power to the drive unit will 
immediately activate the 
coils and close the 
contactor. 
 
Control  circuit  wiring  is  connected  to  the 
contactor by means of a drive unit (black plastic 
box) located on the right side frame (Figure 7).  
Either  AC  or  DC  supply  voltage  may  be 
connected to the drive unit. 
 
The  standard  operating  voltage  for  the  control 
circuit  is  100-240V  AC/DC.    Figure  8  in  the 
OPERATION  section  of  this  manual  show  the 
internal  connections  of  the  drive  unit,  closing 
coils, and auxiliary switch. 
 
 
Figure 7 - Drive Unit 
 
    WARNING 
    CAUTION 
   WARNING