38 Error Check Method and Error Code List
38.4 Error Code List and Action
Syntax error [M8065(D8065)]
0000
No error
6501
Stops
operation
Incorrect combination of instruction, device symbol and 
device number
During programming, each instruction is checked. If a 
syntax error is detected, modify the instruction correctly.
6502
No OUT T or OUT C before setting value
6503
No setting value after OUT T or OUT C
Insufficient number of operands for an applied 
instruction
6504
Same label number is used more than once.
Same interrupt input or high-speed counter input is 
used more than once.
6505
Device number is out of allowable range.
6506
Invalid instruction
6507
Invalid label number [P]
6508
Invalid interrupt input [I]
6509
Other error
6510
MC nesting number error
Circuit error [M8066(D8066)]
0000
No error
6610
Stops
operation
LD, LDI is continuously used 9 times or more.
This error occurs when a combination of instructions is 
incorrect in the entire circuit block or when the 
relationship between a pair of instructions is incorrect.
Modify the instructions in the program mode so that their 
mutual relationship becomes correct.
6611
More ANB/ORB instructions than LD/LDI instructions
6612
Less ANB/ORB instructions than LD/LDI instructions
6613
MPS is continuously used 12 times or more.
6614
No MPS instruction
6615
No MPP instruction
6616
No coil between MPS, MRD and MPP, or incorrect 
combination
6617
Instruction below is not connected to bus line: 
STL, RET, MCR, P, I, DI, EI, FOR, NEXT, SRET, IRET, 
FEND or END
6618
STL, MC or MCR can only be used in main program, but 
it is used elsewhere (e.g. in interrupt routine or 
subroutine).
6619
Invalid instruction is used in FOR-NEXT loop: 
STL, RET, MC, MCR, I (interrupt pointer) or IRET.
6620
FOR-NEXT instruction nesting level exceeded
6621
Numbers of FOR and NEXT instructions do not match.
6622
No NEXT instruction
6623
No MC instruction
6624
No MCR instruction
6625
STL instruction is continuously used 9 times or more.
6626
Invalid instruction is programmed within STL-RET loop: 
MC, MCR, I (interrupt pointer), SRET or IRET.
6627
No STL instruction
6628
Invalid instruction is used in main program: 
I (interrupt pointer), SRET or IRET
6629
No P or I (interrupt pointer)
6630
No SRET or IRET instruction
STL-RET / MC-MCR instructions programmed in the 
subroutine.
6631
SRET programmed in invalid location
6632
FEND programmed in invalid location
Error 
code
PLC operation at 
error occurrence
Contents of error
Action