APC PDPM144F User Manual
1.2 REFERENCES
A.
General: The publications listed below form a part of this Specification to the extent
referenced. The publications are referred to in the text by the basic designation only. The
edition/revision of the referenced publications shall be the latest date as of the date of the
Contract Documents, unless otherwise specified.
referenced. The publications are referred to in the text by the basic designation only. The
edition/revision of the referenced publications shall be the latest date as of the date of the
Contract Documents, unless otherwise specified.
B.
Electronic Industries Association (EIA):
1.
1.
EIA 310, "Racks, Panels, and Associated Equipment" (copyrighted by EIA, ANSI
approved).
approved).
C.
Institute of Electrical and Electronics Engineers (IEEE):
1.
1.
IEEE 519-1992 Standard Practices and Requirements for Harmonic Control in
Electrical Power Systems.
Electrical Power Systems.
D.
International Organization for Standardization (ISO):
1.
1.
ISO 9001, "Quality Management Systems - Requirements."
2.
ISO 14001, “Environmental Management Systems - Requirements With Guidance for
Use.”
Use.”
E.
Underwriters Laboratories, Inc. (UL):
1.
1.
UL 60950, “Standard for Information Technology Equipment.”
2.
ULc CSA 60950-1
F.
Where applicable, the PDU shall also be designed in accordance with publications from
the following organizations and committees:
1.
the following organizations and committees:
1.
NFPA- National Fire Protection Associations
2.
OSHA - Occupational Safety and Health Administration
1.3 SYSTEM
DESCRIPTION
A.
Design Requirements
SELECT OR INSERT APPLICABLE VALUE BELOW.
1.
The PDU shall be sized for [____] kVA load.
B.
System Characteristics
1.
1.
System Capacity:[144kW][277kW]
[The PDPM144F PDU shall support 400A at 208V maximum input and provide
144kW output.]
[The PDPM277H PDU shall support 400A at 400V maximum input and provide
277kW output.]
[The PDPM144F PDU shall support 400A at 208V maximum input and provide
144kW output.]
[The PDPM277H PDU shall support 400A at 400V maximum input and provide
277kW output.]
2.
Upstream Breaker Protection: Upstream breaker protection rated at 400A is
recommended.
recommended.
3.
Input: The system input shall be configurable as single mains derived from a three
phase wye source. Standard cable entry shall be through the top. Bottom cable entry
shall also be facilitated.]
a. AC Nominal Input Voltage:
phase wye source. Standard cable entry shall be through the top. Bottom cable entry
shall also be facilitated.]
a. AC Nominal Input Voltage:
[PDPM144F: 120/208V 3-phase, 400A, 3-Wire+N+G, 60 Hz]
[PDPM277H: 400V/230V 3-phase, 3-Wire+N+G, 60Hz]
[PDPM277H: 400V/230V 3-phase, 3-Wire+N+G, 60Hz]
b. Maximum Input Current:
[PDPM144F: 400A]
[PDPM277H: 400A]
[PDPM277H: 400A]
Page 2