APC Redundant Switch: Installation and Operation Manual
Installation
Turn on the 
equipment and 
Redundant 
Switch
1. Turn on all connected equipment.
2. To provide power to the equipment, press the 
ON
 button 
of 
UPS
-
A
 to turn on the Redundant Switch and 
UPS
-
B
3. To test whether the cables are connected correctly, press 
the 
OFF
 button on one 
UPS
– If it turns back on, the cabling is correct.
– If it does not turn back on, try swapping the two 
UPS
 
communications cables to correct the problem.
Connect the 
PowerChute
®
 
cable
When you are ready to install PowerChute plus, install the 
PowerChute plus communications cable between the server 
port of the Redundant Switch and your server’s serial port.
Note
To use PowerChute plus software to manage a 
Redundant Switch configuration, your server 
must be running Windows NT, Solaris, or 
NetWare. See your PowerChute plus 
documentation for the operating system versions 
that are supported.