APC Redundant Switch: Installation and Operation Manual
13
Configuration
Supported 
configurations
Two supported configurations for Redundant Switch are shown 
below. For more information on these and other supported 
configurations, visit the 
APC
 Web site at www.apc.com.
Configuring 
PowerChute 
plus
 
1. Install PowerChute plus as described in the enclosed 
software installation instructions.
2. For Source B:
a. At the Redundant Switch front panel, set the Source 
Preference to Source 
B
.
b. Start the computer on which PowerChute plus is 
installed.
c. Start PowerChute plus. Communication is to 
UPS
-
B
.
d. Configure 
UPS
-
B
 according to your requirements.
e. Set the 
UPSID
 to 
UPS_B
.
3. For Source A:
a. At the Redundant Switch front panel, set the Source 
Preference to Source 
A
.
Note
Install only 
SNMP
 accessories in the 
UPS
. You 
must install any other accessories in the 
Redundant Switch
Both 
UPS
s must be the same sine-wave model.
Minimum acceptable 
configuration:
 Redundant Switch
 
with two Smart-UPS units 
connected to one 
AC
 line (the same 
facility power source).
Best configuration: Redundant 
Switch
 
with two Smart-UPS units 
connected to two separate 
AC
 lines 
(each 
UPS
 receiving power from a 
separate facility power source).