APC Rack Automatic Transfer Switch, 12A, 230V SU043 User Manual

Product codes
SU043
Page of 34
14
APC Redundant Switch: Installation and Operation Manual
Configuration
b. Restart the computer on which PowerChute plus is 
installed.
c. Start PowerChute plus. Communication is to 
UPS
-
A
.
d. Configure 
UPS
-
A
 according to your requirements.
e. Set the 
UPSID
 to 
UPS
_
A
.
When one 
UPS
 
becomes 
unavailable
When one of the two 
UPS
s becomes unavailable to supply 
AC
 
power, PowerChute plus sends the message “Self test failed: 
invalid test.” Any of the following conditions will cause the 
message to occur:
• A 
UPS
 self-test fails.
• Communication with the alternate 
UPS
 is lost.
• The voltage of the alternate 
UPS
 is out of range.
UPS
-
A
 fails, and the Redundant Switch transfers the 
power input and PowerChute plus communication to 
UPS
-
B
.
To regain high availability for your system, correct the problem 
as soon as possible. See “Troubleshooting” on pa ge18.
Note
When any self-test of the primary 
UPS
 occurs, 
the Redundant Switch switches power and 
communication to the other 
UPS
, causes a self-
test of that 
UPS
, and then switches back. This is 
normal behavior.