APC Redundant Switch: Installation and Operation Manual
Operation
Emergency 
Power Off
You can use a remotely operated Emergency Power Off (
EPO
switch to turn off the 
UPS
 and disconnect power to the 
equipment load. When you turn off the 
UPS
 through the 
Emergency Power Off system, it will turn off immediately 
without switching to battery operation. 
1. Use the 
EPO
 connector.
2. Use a normally-open contact to connect the +24 terminal 
to the 
IN
 terminal. 
3. Wire the external blue four-pin female connector to the 
emergency power off system. 
Electrical
Hazard
Use only a licensed electrician to perform the 
following procedure to connect the Redundant 
Switch and its attached UPSs to your 
Emergency Power Off system.
Caution
The 
EPO
 interface is a Safety Extra Low Voltage 
(
SELV
) circuit. Connect it only to other 
SELV
 
circuits.
The 
EPO
 interface monitors circuits that have no 
determined voltage potential. Such closure 
circuits may be provided by a switch or relay 
properly isolated from the utility. To avoid 
damage to the Redundant Switch, do not connect 
the 
EPO
 interface to any circuit other than a 
closure type circuit.