Electrical Requirements
M414038
48
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Electrical Requirements
Refer to Table 10.
NOTE: Minimum wire sizes are obtained from 
Canadian Electrical Code and are intended for use 
as a guideline only. Electrical connections should be 
made only by a qualified electrical contractor in 
accordance with all applicable local and national 
requirements.
NOTE: Connect to an individual branch circuit.
NOTE: Use copper conductors only.
Table 10 
120 Pound Tumbler Model
Serial Plate Voltage
Terminal Block 
Connections Required
Rated 
Current*
Breaker 
Rating
Breaker 
Poles
Recommended 
Wire Size
208 – 230V/60Hz/3ph
L1, L2, L3 and ground
6.7
10 Amps
3
14 AWG (2.6 mm
2
)
380 – 415V/50Hz/3ph
L1, L2, L3 and ground
4.7
10 Amps
3
14 AWG (2.6 mm
2
)
460 – 480V/60Hz/3ph
L1, L2, L3 and ground
4.0
10 Amps
3
14 AWG (2.6 mm
2
)
170 Pound Tumbler Model
Serial Plate Voltage
Terminal Block 
Connections Required
Rated 
Current
Breaker 
Rating
Breaker 
Poles
Recommended 
Wire Size
208 – 230V/60Hz/3ph
L1, L2, L3 and ground
12.7
15 Amps
3
14 AWG (2.6 mm
2
)
380 – 415V/50Hz/3ph
L1, L2, L3 and ground
7.3
10 Amps
3
14 AWG (2.6 mm
2
)
460 – 480V/60Hz/3ph
L1, L2, L3 and ground
6.6
10 Amps
3
14 AWG (2.6 mm
2
)
* Current ratings vary slightly depending on model; refer to serial plate.