Make-Up Air Requirements
It is important that the laundry room has adequate
make-up air for the dryer(s). A dryer exhausts 220 cfm
(measured at back of the dryer) and sufficient make-up
air must be supplied to replace the air exhausted by the
dryer.
make-up air for the dryer(s). A dryer exhausts 220 cfm
(measured at back of the dryer) and sufficient make-up
air must be supplied to replace the air exhausted by the
dryer.
Make-Up Air Dos and Don’ts
Do
●
Supply adequate air for ventilating air, drying air
and gas dryer combustion air.
and gas dryer combustion air.
NOTE: Each dryer pocket must have 40 square
inches (260 cm
inches (260 cm
2
) of unobstructed flow of make-up
air for proper operation.
●
Energy efficient buildings with low air
infiltration rates should be equipped with an air
exchanger that can accommodate on demand
make-up air needs in the laundry room. These
devices can be obtained through your building
contractor or building material suppliers.
infiltration rates should be equipped with an air
exchanger that can accommodate on demand
make-up air needs in the laundry room. These
devices can be obtained through your building
contractor or building material suppliers.
Don’t
●
Draw make-up air from a room containing a gas
fired water heater.
fired water heater.
●
Draw make-up air from a room containing a dry
cleaner or a hair salon.
cleaner or a hair salon.
Exhaust Direction
The dryer can be exhausted to the outdoors through the
back, left or right of the dryer. EXCEPTION: Gas
dryers cannot be vented out the left side because of
the burner housing.
back, left or right of the dryer. EXCEPTION: Gas
dryers cannot be vented out the left side because of
the burner housing.
Unit is shipped from factory ready for rear exhaust; no
kits required.
kits required.
Exhausting the dryer through sides can be
accomplished by installing a Directional Exhaust Kit
528P3 available as optional equipment at extra cost.
accomplished by installing a Directional Exhaust Kit
528P3 available as optional equipment at extra cost.
Figure 43
H297I
1
Weather Hood with Hinged Dampers
2
Rigid or Flexible Metal Duct
H297I
1
2
528P3 DIRECTIONAL EXHAUST KIT