Installation
510963
18
Electrical Plug Connection
Three-Wire Plug
Figure 14 
1. Remove access cover from rear of dryer.
Figure 15 
2. Use a strain relief and insert end of power cord 
through power supply hole.
Figure 16 
D816I
1
3 Wire Grounded Neutral 120/240 Volt, 60 Hertz 
AC 1 Phase Service Entrance Switch Box
(Refer to NOTE above)
4
Metallic or Non-Metallic Sheathed Cable 
(Copper Wire Only)
5
Pigtail to Dryer (Refer to NOTE above)
2
30 Ampere Fuses or Circuit Breaker
6
Neutral
3
Neutral Wire
7
Terminal Block in Dryer
NOTE: The power cord (pigtail) is NOT supplied with 
the electric dryer. Type of pigtail and gauge of wire 
must conform to local codes and instructions.
The method of wiring the dryer is optional and subject 
to local code requirements.
NOTE: Connect the dryer to the power supply with the 
MAXIMUM RATED VOLTAGE listed on the nameplate.
1
3
5
6
7
4
2
PIGTAIL CONNECTION
DIRECT CONNECTION
L1
L2
L1
L2
INTERMEDIATE 
SHUT-OFF BOX 
(may or may not 
be fused)
POWER SUPPLY
POWER SUPPLY
INTERMEDIATE 
FUSE BOX (may 
be omitted if 
service entrance 
box is fused)
WALL 
RECEPTACLE
A typical 
30-Amp 
Three-Wire 
Receptacle 
NEMA Type 
10-30R
120 ± 12
V.A.C.
120 ± 12
V.A.C.
240 ± 12
V.A.C.
NOTE: Use COPPER WIREonly. 
Shorter than 15 ft. (4.5 m) – use 10 AWG
Longer than 15 ft. (4.5 m) – use 8 AWG
D695I
D696I