Installation 
Electrical Installation 
18 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
Revision 7 
  
 7/08 
HercuLine
®
 2000 Terminal Connections 
Table 3  Terminal Connections: HercuLine
®
 2000 
 
Connection 
Terminal Numbers 
and LABEL 
See Figure 8 
Descriptions 
Hot 1 
Hot wire for 120/240VAC mains supply. Use only if Auto/Manual 
switch is present. 
Neutral 
Neutral wire for 120/240VAC mains supply 
Auto/Manual Switch 
Contact 

Switch contact to indicate setting of actuator AUTO/MANUAL 
switch. 
Switch is closed when actuator is “NOT-IN-AUTO” 
CW from Controller 
CW motor drive 
CCW from Controller 
CCW motor drive 
Potentiometer #1 


Clockwise-End 
Slider 
Counterclockwise-End 
Potentiometer #2 
10 
11 
12 
Clockwise-End 
Slider 
Counterclockwise-End 
Protective Ground 
 
Ground wire connection for mains supply 
 
 
158 ohm
158 ohm
Install resistors to convert 1000 ohm 
potentiometer to 135 ohms
1
1
REQUIRED ONLY IF AUTO/MANUAL
SWITCH IS PRESENT
158 ohm
158 ohm
Install resistors to convert 1000 ohm 
potentiometer to 135 ohms
1
1
1
1
REQUIRED ONLY IF AUTO/MANUAL
SWITCH IS PRESENT
 
Figure 8 HercuLine
®
 2000 connections