Honeywell herculine 2000 User Manual

Page of 128
Installation 
Electrical Installation 
Revision 7 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
19 
7/08  
 
 
HercuLine
®
 2001/2002 with Auto/Manual Terminal Connections 
Table 4  Terminal Connections: HercuLine
®
 2001/2002 with auto/manual 
 
Connection 
Terminal Numbers 
and LABEL 
See Figure 9 
Descriptions 
 
TB1 
 
Hot 
Hot wire for 120/240VAC mains supply 
Neutral 
Neutral wire for 120/240VAC mains supply 
Protective Ground 
Ground wire connection for mains supply 
Auto/Manual Switch 
Contact 

Switch contact to indicate setting of actuator AUTO/MANUAL 
switch.   
Switch is closed when actuator is “NOT-IN-AUTO” 
 6 
 
 
TB3 
 
4 to 20mA Output* 
1 (+) 
2 (-) 
Analog signal output  
Feedback 3 
Feedback signal used in conjunction with 4 to 20mA OUTPUT 
voltage when using Slidewire Emulation 
4 to 20mA Input 
4 (+) 
5 (-) 
Analog signal input  
Modbus 
Communication 
6 (+) 
7 (-) 
8 Shield 
Connection for RS485 Modbus loop wires 
HART Communications 
4 (+) 
5 (-) 
HART Communication is 4-20 mA only. 
Digital Input 
9 Com 
10 Input 
Customer’s contact closure 
 
Auxiliary
Connector
_
Brown
Black
Blue
+
Black Wire Not Used
HART connection using
external Turck connector
+
_
HART
Communications
Connection
Auxiliary
Connector
_
Brown
Black
Blue
+
Black Wire Not Used
HART connection using
external Turck connector
Auxiliary
Connector
_
Brown
Black
Blue
+
Black Wire Not Used
HART connection using
external Turck connector
+
_
HART
Communications
Connection
 
Figure 9 HercuLine
®
 2001/2002 connections