Installation 
Electrical Installation 
20 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
Revision 7 
  
 7/08 
HercuLine
®
 2003 Wiring Connections and Operation (Actionator 640D Replacement) 
Wiring 
 
Figure 10 HercuLine
®
 2003 connections  
Operation 
The 2003 actuator is uni-directional (it does not reverse rotation with a reversal in control action).  
Figure 10 illustrates the internal wiring and the external connections.  
The smaller insert of the figure describes the limit switch action for one complete cycle. When the two-position 
controller detects a sufficient fall in temperature in a heating application, the switch portion between the “4” and 
“5” terminals will close. 
The motor then rotates for 180º or until the opening switch breaks (stops are adjustable, factory set at 180º), and 
stops in full open position. 
A subsequent rise in temperature causes the controller to close the switch between the “4” and “6” terminals 
when the motor will start to rotate (in the same direction) for 180º or until the closing switch breaks.  
The motor stops in the closed position and completes one cycle.