York YCJD18 THRU 60 User Manual

Page of 28
840569-YTG-A-0612
Johnson Controls Unitary Products
3
System Charge for Various Matched Systems
Outdoor Unit 
YCJD18
S41S1(H)(E)
YCJD24
S41S1(H)(E)
YCJD30
S41S1(H)(E)
YCJD36
S41S1(H)(E)
YCJD42
S41S2(H)(E)
YCJD48
S41S1(H)(E)
YCJD60
S41S1(E)
Required Orifice or TXV 
1,2
0.048/4F1
0.055/4F1
0.061/4F1
0.065/4G1
0.073/4G1
0.073/4H1
0.087/4J1
Indoor Unit
 3,4,5
Additional Charge, oz.
AHE18B
0
AHE24B
4
AHE30B
4
0
AHE36C
4
2
0
AHE42D
8
10
AHE48D
9
0
AHE60D
14
4
AHP18
0
AHP30
4
0
AHP36
2
0
AHP42
0
0
AHP48
10
0
AHP60
10
0
0
AHR18B
0
AHR24B
4
AHR30B
0
AHR36B
2
0
AHR42C
8
10
AHR48D
9
0
AHR60D
15
4
AHX18
0
AHX30
4
0
AHX36
4
2
0
AHX42
8
10
AHX48
9
0
AHX60
15
4
AV*24
TXV  +  0
AV*36
4
2
0
AV*48
TXV  +  10
0
AV*60
TXV  +  10
0
0
F4FP024
0
F4FP036
0
F4FP040
0
F4FV060
0
0
F5FP048
8
4
F5FP060
0
0
F6FP018
0
F6FP030
4
0
F6FP036
4
0
F6FP042
8
4
F6FP048
TXV  +  9
0
F6FP060
15
4
FC/MC/PC18
0
FC/MC/PC32
4
0
FC/MC/PC35
4
0
FC/MC/PC36
0
FC/MC/PC37
4
2
0
For Notes See Page 4.