York YCJD18 THRU 60 User Manual

Page of 28
840569-YTG-A-0612
4
Johnson Controls Unitary Products
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the outdoor unit, the smallest matched indoor unit, and 15 feet of interconnecting line tubing.
2. Verify the TXV or orifice and additional charge required for specific matched indoor unit in the system using the above table.
3. Add additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electrical Data Table.
4. For indoor matches requiring additional charge, the refrigerant needs to be weighed in for specific matched indoor unit and lineset length.
5. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + charge adder for matched indoor unit + 
charge adder for line set.
FC/MC/PC43
4
2
0
0
FC/MC/PC48
8
10
4
FC/MC/PC60
9
0
0
FC/MC62
14
4
FC64
23
11
UC18
0
UC36
0
UC48
8
4
4
UC60
9
0
0
Some of the combinations shown in the above System Charge table require Advanced Main Air Circulating Fan indoor product. For approved coil 
only matches, please see the “COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils” table.
FOOTNOTES:
1. For applications requiring a TXV use S1-1TVM*** series kit.
2. Approved orifice(s) shipped with outdoor unit.
3. Systems matched with furnaces or air handlers not equipped with blower-off delays may require blower Time Delay Kit S1-2FD06700224.
4. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
5. Refer to Cooling Performance Data tables for actual system performance for specified system matches.
System Charge for Various Matched Systems (Continued)
Outdoor Unit 
YCJD18
S41S1(H)(E)
YCJD24
S41S1(H)(E)
YCJD30
S41S1(H)(E)
YCJD36
S41S1(H)(E)
YCJD42
S41S2(H)(E)
YCJD48
S41S1(H)(E)
YCJD60
S41S1(E)
Required Orifice or TXV 
1,2
0.048/4F1
0.055/4F1
0.061/4F1
0.065/4G1
0.073/4G1
0.073/4H1
0.087/4J1
Indoor Unit
 3,4,5
Additional Charge, oz.
Models 12-48 require Hard Start Kits for TXV matches. Models with “H” on the end of the model number have factory installed Hard Start Kits.
For models without an “H” refer to the Hard Start Kit Accessory Installation Manual for the Hard Start Kit part number for each model.