ProData II
Configuration and commissioning
Connecting the supply voltage
The supply voltage must be connected to configure and 
commission the ProData 2.
The supply voltage level for the ProData 2 is specified 
on the rating plate.
RS485 interface
The following parameters must be set to operate 
the RS485 interface:
- Device termination (termination resistor)
- Device address (see the device address chapter)
- Baud rate
- Stop bits
The factory settings and the setting area for the baud 
rate are specified in the parameter list.
Device termination (termination resistor)
For fault-free operation of the devices within a bus 
structure, termination resistors must be set at the start 
and the end of a segment. If the ProData 2 is at the start 
or the end of a segment, a termination can be switched 
via the DIP switch S1.
ON
OFF
S1
Device termination
ON:   Device termination active (220 Ohm)
OFF:  Device termination inactive