Janitza Prodata 2 5224001 Data Sheet

Product codes
5224001
Page of 56
40
ProData II
Modbus gateway
The ProData 2 can be set as a Modbus gateway with 
the following limitations:
•  In this mode, the ProData 2 cannot be used as a 
Modbus RTU slave device.
•  In this mode, the ProData 2 converts Modbus TCP 
packages from port 502 (only TCP) to Modbus 
RTU and sends these via the RS485 interface.  
If a response is received via the RS485 interface 
within a timeout period that can be set, this is 
converted to Modbus TCP again and sent via 
the IP connection.
•  The ProData 2 can only forward queries (e.g. 
from the GridVis software) to a Modbus slave 
device. It 
CANNOT query Modbus slave devices 
independently.
Fig.:  Connection variant with ProData 2 as a gateway.
The ProData 2 converts the queries of the GridVis 
software (TCP packages via Ethernet) for the Modbus 
slave devices (Modbus RTU) and forwards these via 
the RS485 interface (RS485 mode: Gateway; Addr. 3=1).
PC with GridVis software
ProData 2
as gateway
UMG 104
Slave 1
UMG 103
Slave 2
UMG 604
Slave 3
Ethernet
Modbus
Modbus
Modbus
Ethernet