Janitza Prodata 2 5224001 Data Sheet

Product codes
5224001
Page of 56
43
ProData II
Battery
The internal clock is fed from the supply voltage. 
If the supply voltage fails then the clock is powered by 
the battery. 
The clock provides date and time information, e.g. for 
the records and events.
The life expectancy of the battery is at least 5 years 
with a storage temperature of +45 °C. The typical life 
expectancy of the battery is 8 to 10 years. 
The battery status (full capacity, undervoltage, no capacity) 
can be read via the Modbus (address 4942) / Ethernet using 
the GridVis software. If the battery is exhausted and no 
time synchronisation (NTP) is set, the software takes 
the last valid time stamp from the memory and resumes 
from there.
The following chapter provides information about 
changing the battery.
Modbus
Address
Bit
Status description
4942
(short,
16-bit)
0
•  Battery capacity exhausted
•  Clock has stopped and must 
be set if necessary
•  Battery should be replaced
1
•  Battery capacity nearly 
exhausted
•  Battery should be replaced
2
•  Battery capacity low
•  Battery should be replaced
Table: Battery status 
 
(can be read via Modbus in address 4942).