5. FIRE-FIGHTING AND EXPLOSION HAZARD MEASURES 
Components 
 
 
VRLA Battery 
 
  VRLA Batteries emit hydrogen gas which is highly flammable and will form 
explosive mixtures in air from approx 4% to 76%.  This can be ignited by a spark 
at any voltage, naked flames or other sources of ignition. 
 
  Batteries in use will be part of an electrical circuit and must be isolated from the 
power source before attempting to put out a fire.  Switch the power OFF before 
disconnecting the batteries from the power source. 
 
 
  Damaged batteries may expose negative plates (grey) colour, which may ignite 
if allowed to dry out. These plates may be wetted down with water after the 
battery has been removed from all electrical circuits. 
Suitable Extinguisher types: 
CO
2
; Foam; Dry Powder. 
Unsuitable Extinguisher types 
Water extinguishers must never be used to put out an electrical fire. 
Hazardous decomposition 
products: 
Carbon monoxide, Sulphur Dioxide, Sulphur Trioxide, lead fume and vapour, toxic 
fumes from decomposition of battery case materials. 
Special protective equipment 
for fire fighters: 
Full face visor or safety goggles; respiratory protective equipment or self-contained 
breathing apparatus;  full acid resistant protective clothing must be worn in fire 
fighting conditions. 
 
6. ACCIDENTAL RELEASE MEASURES 
This information is of relevance only if the VRLA Battery has suffered damage and is broken. 
 
Components 
 
 
VRLA Battery 
 
VRLA batteries are designed not to leak under normal conditions.  
Plate Grids and 
Active materials 
Personal Precautions: 
Use of heavy-duty gloves is recommended 
Clean-up Methods: 
Solid lead may be picked up and recycled. 
Active material waste should be cleaned up and the area washed. 
Environmental Precautions: 
Do not allow to enter a watercourse. Exposed lead materials must be placed in an 
inert sealed container (e.g. self-seal plastic bag) for disposal, see Section 13. 
Battery Electrolyte:  
 
Personal Precautions: 
Ensure suitable, acid resistant, personal protective clothing (including respiratory 
protection) is worn during removal of spillages. 
Clean-up Methods: 
Small spillages: 
 
Large spillages: 
 
 
Absorb spillages. Wash the spillage area with water. 
 
Electrolyte leakage should be absorbed onto dry sand, earth, sawdust or other 
inert material and must not be allowed to enter any drains or sewage system.  
Neutralise the electrolyte using soda ash, sodium bicarbonate, sodium carbonate 
or calcium carbonate powder and then wash the area thoroughly with water. 
Collect absorbed material and place in an inert sealed container (e.g. self-seal 
plastic bag) for disposal, see Section 13. 
Case Material:  
Clean-up Methods: 
Sweep and/or shovel up. Collect contaminated material and place in an inert 
sealed container for disposal, see Section 13. 
 
Separator Material: 
 
Clean-up Methods: 
Sweep and/or shovel up. Collect contaminated material and place in an inert 
sealed container for disposal, see Section 13. 
 
Note: If appropriate refer to 8 and 13 
 
7. HANDLING AND STORAGE 
Components 
 
 
VRLA Battery 
Storage 
 
Store batteries in a cool, well ventilated area with a solid, impervious surface, and 
adequate containment in the event of accidental acid spillage.    
Store under a roof and protect against adverse weather conditions including rain, 
snow and other sources of water. 
Storage of large quantities of VRLA batteries may require approval from local 
environmental protection agency and/or local water authorities. 
Pallets of VRLA Batteries are heavy.  Store at ground level or in lower levels of 
storage systems (e.g. racking). 
Take special care in dry conditions to avoid the risk of electrostatic discharges. 
Protect against physical damage and exposure to organic solvents and other 
incompatible materials.