Whirlpool T-K2 User Manual

Page of 32
Gas Supply Piping
 
 
Check the rating plate to make sure that the 
unit was built for the type of gas available in 
the area.  
The gas supply piping should be sized 
according to the Applicable Plumbing Code for 
a maximum draw of 185,000 BTUH.  First 
determine the effective length of the gas 
supply line by measuring the actual length of 
piping, and then adding 5 ft. for every elbow or 
“T” to the actual length.  Use the charts below 
to determine the pipe diameter necessary to 
accommodate the BTU demand of the unit.  If 
there are more gas drawing appliances on the 
line, size according to the maximum amount of 
BTU demand.   
The gas supply pressures must be within the 
ranges of the following chart: 
 
Natural Gas 
Supply Pressure 
Min. 5” WC 
Max. 10.5” WC 
Propane Gas 
Supply Pressure 
Min. 11” WC 
Max. 14” WC 
 
Insufficient gas supply pressure can cause the 
Flash Water Heater to lose efficiency or not 
work at all. 
WARNING: Fire or explosion may result if the 
maximum supply pressures are exceeded. 
The manifold gas pressure should be at 
maximum 2.3” WC for natural gas, and 2.5” 
WC for propane. 
Always use approved connectors to connect 
the unit to the gas line. Always purge the gas 
line of any debris before connecting to the 
water heater. 
WARNING: Conversion of this unit from 
natural gas to propane or propane to natural 
gas cannot be done in the field. Contact your 
local retailer or distributor to get the correct 
unit for your gas type. 
Always install a manual shutoff valve on the 
gas supply line in case of an emergency, or if 
service or maintenance is necessary. 
This appliance and its individual shut-off valve 
must be isolated from the gas supply piping 
system by unplugging the unit and turning off 
the main gas valve during any pressure testing 
of the gas supply piping system at test 
pressures equal to or less than ½ PSI. 
When all of the connections have been made, 
check the gas line for leaks. Apply soapy 
water to all gas fittings and connections, if 
bubbles form, there may be a leak. 
 
Natural Gas Supply Piping 
Based on 0.60 specific gravity for natural gas at .5” WC pressure drop 
DOE standard is 1100 BTU per cubic ft. of natural gas 
Pipe 
Size 
 
Cubic Feet of Natural Gas 
Length 10’ 20’ 30’ 40’ 50’ 60’ 70’ 80’ 90’ 100’ 
125’ 
150’
200’
½”  174 
119 96 82 73 66 61 56 53 50 44 40 
34 
¾”  363 249 200 171 152 138 127 118 111 104  93  84 72 
1”  684 470 377 323 286 259 239 222 208 197 174 158
135
¼” 1404 965 775 663 588 532 490 456 428 404 358 324
278
½” 2103 
1445 
1161
993 880 798 734 683 641 605 536 486
416
2” 
4050 2784 2235
1913 1696
1536
1413
1315
1234
1165 1033 936
801
 
Propane Supply Piping 
Based on 11” WC supply pressure 
Pipe 
Size  
 
kBTU of Propane 
Length 
10’ 20’ 30’ 40’ 50’ 60’ 70’ 80’ 90’ 100’ 
125’ 
150’
200’
½” 275 
189 
152 
129 
114 
103 96 89 83 78 69 63 55 
¾”  567 393 315 267 237 217 196 185 173 162 146 132 112 
1”  1071 
732 590 504 448 409 378 346 322 307 275 252 213 
¼” 2205 
1496 
1212 
1039 913 834 771 724 677 630 567 511 440 
½”  3307 2299 1858 1559 1417 1275
1181
1086
1023
976  866  787  675 
2”  6221 4331 3465 2992 2646 2394
2205
2047
1921
1811 1606 1496
1260