Water Plumbing 
 
Follow local guidelines for the length of the 
plumbing line in order to ensure that there is 
enough water pressure for all the fixtures on 
the line.  First, calculate the effective length of 
the plumbing line by measuring the total length 
of pipe, and then adding to this 5’ for each 
elbow or tee in the line.  Use the following 
chart to determine the total number of fixture 
units on the line, and then compare with the 
chart at the bottom of this page to find the pipe 
diameter and water pressure necessary. 
 
 
 
 
 
 
 
 
 
 
Install with control valves on the inlet and 
outlet, and use removable unions or 
connectors to facilitate maintenance or service 
if necessary. 
 
If the water heater is installed in a closed 
water system, means shall be provided to 
control thermal expansion. Contact the water 
supplier or a local plumbing inspector on how 
to control this situation. 
Purge the water line of air, and clean the filter 
before initial operation. 
WARNING: Do not reverse the hot outlet and 
cold supply line connections to the Flash 
Water Heater. Make sure the hot and cold 
lines are connected as in the FOR YOUR 
SAFETY section at the front of this manual. 
 
Pressure Relief Valve 
 
An approved pressure relief valve must be 
installed in any installation with this unit.  The 
pressure relief valve must be installed on the 
hot line out of the unit, with no check valves or 
control valves between the unit and the relief 
valve. 
 
 
The Pressure relief valve must be rated for 
150 PSI, and have a discharge capacity of 
185,000 BTU.  Connect the discharge opening 
of the relief valve to a suitable drain to prevent 
water damage should discharge occur. 
If the pressure relief valve discharges 
periodically, this may be due to thermal 
expansion in a closed water supply system. 
Contact the water supplier or local plumbing 
inspector on how to correct this situation.  
Do not plug the pressure relief valve. The line 
should have no reduced fittings or other 
restrictions and should allow for complete 
drainage of valve and line. The pressure relief 
valve should be manually operated once a 
year to check for correct operation.
 
Should overheating occur or the gas supply 
fail to shut off, turn off the manual gas control 
valve to the appliance. 
Length to the End of Hot Water Line and Recommended Fixture Units 
 
Pressure Range 30 to 45 PSI 
Pressure Range 46 to 60 PSI 
Pressure Range 60+ PSI 
Pipe 
Size 
100' 
200' 
300' 
400' 
100' 
200' 
300' 
400' 
100' 
200' 
300' 
400' 
3/4" 
3-12 
1-6 
1-5 
0-4 
5-17 
3-11 
2-8 
1-6 
6-20 
4-13 
3-10 
2-8 
1" 
12-25 
6-17 
5-13 
4-12 
17-36
11-25
8-20 
6-18 
20-39
13-32 
10-26
8-22 
1-1/4" 
25-48 
17-32 
13-25
12-21 
36-78
25-52
20-39
18-33
39-78
32-74 
26-54
22-43
Fixture Unit Per Fixture (from UPC) 
Plumbing Fixture 
Description 
Fixture 
Unit 
Combination Bath / Shower 
Whirlpool Bath 
Shower 
Lavatory 
Clothes Washer 
Dishwasher 
1.5 
Kitchen Sink 
1.5