Westinghouse WGR050LP076 Installation Instruction

Page of 60
44 
 
 
                                                                                  WHL-001 REV. 12.17.14 
 
 
To enter Installer Mode, press and hold  
 for five seconds. When the (
) screen appears, Installer Mode is active. Press
 at 
this screen to access the Technical Service Parameters codes (P00, P01, etc.). 
 
To change parameter value, press 
 or  
 once. The value will appear. Press 
  to decrease or  
  to increase the value. 
Press
 at this screen to accept the changed value and return to the Technical Service Parameters. 
 
Press 
 to advance through the parameters. Press 
  to return to the previous parameter. 
 
Press
 at any Technical Service Parameter code screens to return to the upper level menu. 
 
Table 11 details the Technical Service Parameters in sequential order. 
 
CODE  SHORT DESCRIPTION 
LONG DESCRIPTION 
RANGE (DEFAULT) 
P00 
User Setpoint (
o
F) 
Minimum Tank Temperature 
70 
– 160 (120) 
P01 
Temperature Differential (
o
C/
o
F) 
Difference Between Actual Tank Temperature and 
User Setpoint that will Initiate Demand 
– 20 (8) 
P02 
Maximum Power Percentage (%) 
Maximum Combustion System Power 
50 
– 100 (80) 
P03 
Temperature Unit Displayed 
Fahrenheit or Celsius 
0 = 
o
C / 1 = 
o
(1) 
P04 
ECO Mode  
Economy Mode 
0 = Off / 1 = On (0) 
P05 
Outdoor Reset Curve 
Turns on the Outdoor Reset Curve 
NOTE: The following parameters are applicable only 
if the Outdoor Reset Curve is turned on. 
0 = Off / 1 = On (0) 
P06 
Minimum Outdoor Temperature (
o
C/
o
F) 
Minimum outdoor design conditions for reset curve 
10 
– 70 (10) 
P07 
Maximum Outdoor Temperature (
o
C/
o
F) 
Maximum outdoor design conditions for reset curve 
10 
– 70 (68) 
P08 
Minimum Storage Temperature (
o
C/
o
F) 
Minimum tank temperature for reset curve 
70 
– 160 (120) 
P09 
Maximum Storage Temperature (
o
C/
o
F) 
Maximum tank temperature for reset curve 
70 
– 160 (140) 
P10 
Warm Weather Shutdown Temperature 
(
o
C/
o
F) 
Outdoor temperatures greater than this value return 
the tank target temperature to the User Setpoint 
50 
– 100 (68) 
Table 11 
– Technical Service Parameters - NOTE: Temperature Readings Depend on Temperature Unit Selection
 
 
Figure 24 
– Outdoor Reset Curve 
D. OUTDOOR RESET 
This unit is supplied with outdoor reset wire connection terminals. When an outdoor sensor is connected, operation of the unit 
immediately changes.
 Refer to the following steps to properly set up the unit with an outdoor sensor. 
 
 
An ASSE 1017 thermostatic mixing valve MUST be installed when using outdoor reset. Failure to do so could result in substantial 
property damage, serious injury, or death.