Siemens Welding System ST PCS 7 User Manual

Page of 344
Operator system
OS archiving
Introduction
5/19
Siemens ST PCS 7 · November 2007
5
Overview
Overview of short-term and long-term archiving
The operator system already includes a high-performance ar-
chiving system based on Microsoft SQL Server with cyclic ar-
chives for short-term saving of process values (typically 1 to 
4 weeks) and messages/events (typically 2 months). Data from 
the short-term archive as well as OS reports and batch data from 
SIMATIC BATCH can be exported time-controlled or event-con-
trolled for permanent archiving in a long-term archive. 
Design
Two alternatives with different features are available for the OS 
long-term archiving: 
• StoragePlus: 
More economical version for the lower performance range; for 
the archiving of about 1600 values/s from as many as four sin-
gle stations, servers or pairs of servers 
• Central archive server (CAS), for single or redundant configu-
ration:
High-performance version for archiving about 10000 values/s 
from as many as 11 servers or pairs of servers
During long-term archiving with StoragePlus, the archived data 
can be visualized by means of the StoragePlus viewer. Process 
values and messages exported to the central archive server can 
also be accessed from an OS client.
The data managed in StoragePlus and in the central archive 
server can be saved on commercially available storage media 
(e.g. DVD). This requires additional hardware and software 
which support the respectively used operating system, e.g. 
a DVD writer with appropriate writer software.
The StoragePlus computer and the central archive server are 
stations on the terminal bus, and are not connected to the plant 
bus. When using a SIMATIC PCS 7 Industrial Workstation (BCE 
version) as the hardware platform, the Ethernet interface 
(Ethernet RJ45 port) already onboard can be used for connect-
ing to the terminal bus.
Through a redundant design of the central archive server, the 
availability of long-term data is increased, and these can also be 
accessed by the OS clients or the OpenPCS 7 station. SIMATIC 
BATCH does not yet swap out the batch data to the two central 
archive servers. However, following automatic matching of the 
archives, the batch data are available on both central archive 
servers following swapping out.
Function
Features of the archive variables and licensing of short-term 
and long-term archiving
• There is only one type of archive variable for OS short-term ar-
chiving and CAS long-term archiving. SIMATIC PCS 7 Archive 
and SIMATIC PCS 7 Archive PowerPacks can be used univer-
sally - both for the operator system and for the CAS. 
• The "SIMATIC PCS 7 Archives" are Count Relevant Licenses, 
i.e. the archive variables of several licenses are cumulative. 
Starting with the smallest cumulative number of 
1500 variables, any combinations are possible with consider-
ation of the expansion limits of 10000 variables for OS short-
term archiving and 120000 variables for CAS long-term ar-
chiving, e.g. 2 x 1500 or 1 x 1500 with 1 x 5000 variables.
• The number of archive variables can also be increased using 
"SIMATIC PCS 7 Archive PowerPacks". Starting with 
1500 variables, increasing is possible in steps through 5000, 
10000, 30000 and 80000 variables up to 120000 variables.
• If a CAS is not used, the licenses of the SIMATIC PCS 7 Ar-
chive are installed on the OS single stations and OS servers of 
the system. Otherwise the installation is only on the CAS. 
OS single stations and OS servers then "book" their archive 
variables from the CAS’s stock of variables. It is therefore un-
necessary to carry out the complex installation of archive vari-
able licenses on all OS single stations and OS servers in the 
system.
• Operator systems (OS single stations and OS servers) are 
assigned 512 archive variables each by the OS software, the 
CAS is immediately provided with 1500 archive variables by 
the central archive server basic package. If the short-term ar-
chiving of the operator systems is combined with the CAS 
long-term archiving, the 512 archive variables of the OS single 
stations and OS servers are not cumulated with the 
1500 archive variables of the CAS. The 1500 archive variables 
of the CAS are then available universally for short-term and 
long-term archiving.
• In the case of redundant systems, two archives must be con-
figured with the corresponding number of archive variables.
Process values
Central archive server:
long-term archiving
Messages/events
Batch data
Slow
archiving cycle
> 1 min
Fast
archiving cycle
≤ 1 min
Alarm archive
Automatic
saving
e.g. daily
Automatic
saving
(applicative)
e.g. weekly
Saving on
hard disk
e.g. for 6 months
On user request,
transfer following
end of a batch
Backup
archiving
on DVD
Batch server
OS server:
short-term archiving (cyclic)
Microsoft
SQL server
e.g.
2 months
e.g.
2 weeks
e.g.
7 days
30 byte/
value
Max.
30 byte/
value
172 byte/
event
XML
files
© Siemens AG 2007