Operator system
OS archiving
OS long-term archiving
with StoragePlus
5/21
Siemens ST PCS 7 · November 2007
5
Overview
StoragePlus is a program package for long-term archiving of 
• OS archive data (process values and messages), 
• OS reports and 
• batch data of the SIMATIC PCS 7 process control system. 
StoragePlus manages the process values and messages ex-
ported from the OS archives, the OS reports as well as batch 
data from SIMATIC BATCH in a central database. All these data 
can be visualized in a graphic and clear manner using the Inter-
net Explorer.
Application
StoragePlus can be used for long-term archiving of process val-
ues and messages, OS reports and SIMATIC BATCH data from 
up to 4 single stations/servers/pairs of servers of the SIMATIC 
PCS 7 V7.0 process control system. For this purpose Storage-
Plus has to be installed on a separate computer with Windows 
XP Professional oder Windows Server 2003 (see page 2/14) 
which is connected by terminal bus to the OS and batch serv-
Function
StoragePlus manages the process values, messages and OS re-
ports which are swapped out of the OS archives, as well as 
batch data from SIMATIC BATCH, in a central database and 
makes these data available independent of the PCS 7 runtime 
systems:
• All data can be visualized in a graphic and clear manner using 
the Internet Explorer, selection of the data is selected by inte-
grated filter functions. 
• Messages and process values can be shown in table form, 
and process values also in graphic form. 
• Tables of process values can be exported in CSV format for 
processing in other Windows applications, e.g. Microsoft 
Excel.
The data managed by StoragePlus and the cataloging can be 
swapped out onto all commercially available storage media. You 
require additional hardware and software for this which support 
the StoragePlus operating system, e.g. DVD writer with appropri-
ate writer software.
StoragePlus is able to read in data which were swapped out 
using StoragePlus V1.0 / V1.1 and to convert the data into the SI-
MATIC PCS 7 V7.0 (StoragePlus V1.2) data format.
Overview of functions
• Archiving of messages, process values and reports of the SI-
MATIC PCS 7 V7.0
operator systems
• Archiving of batch data from SIMATIC BATCH V7.0
• Cataloging of all StoragePlus data
• Swapping out of all StoragePlus data as well as the cataloging 
onto external storage media
• Reading-in of the swapped-out StoragePlus data and catalog-
ing from external storage media
• Parameterizing of views (display windows and masks) includ-
ing the selection criteria for displaying the data
• Visualizing of messages in table form dependent on filter func-
tions
• Displaying of process values in table or graphic form depen-
dent on filter functions
• Exporting of process values in CSV format, e.g. to Microsoft 
Excel
• Visualizing a batch overview (selecting the detailed protocol 
of a batch from the batch overview is possible)
• Web-based presentation of data
• Access protection with user-specific rights
• Migration of messages and measurement values from Stor-
agePlus V1.0 / V1.1
OS clients
Automation
systems
Batch server
(redundant)
StoragePlus
(separate
computer)
OS server
(redundant)
OS-LAN
Plant bus
© Siemens AG 2007