Siemens FC700A User Manual

Page of 70
Bus systems 
15 
Siemens Building Technologies
 
 007836_a_en_--.doc
Fire & Security Products 
 
03.2004
 
 
6.1 Bus 
overview 
 
Features C-Bus 
I-Bus 
SynoLOOP 
SynoLINE600 
LON-Bus 
Data 
Bus 
Field of applica-
tion 
Local system bus 
Inside control unit 
For addressable 
detectors 
For collective 
detectors 
Local data bus 
for floor indicator 
panels 
Local data bus 
parallel ind. 
panel, synoptic 
panel or relay 
Speed of trans-
mission 
57kBaud 1000kBaud 
messages/sec 
(Direct current 
signal) 
78kBaud SPI-Bus 
2KHz 
Length of line 
Max. 1000m 
(G51 ∅ 0,8: 1400m) 
Max. 3m (only 
inside cabinet) 
Max. 150Ω/300nF
Max. 
150/250Ω/4µF 
Max. 500m as 
free topology 
Max. 1000m as 
stub line 
Max. 1000m 
Number of users 
connected or 
addresses 
… 16 
C-Bus devices 
… 16 
I-Bus modules 
… 128 
D-Bus devices 
1 address 
(Max. 25 detec-
tors) 
… 32 
LON-Bus de-
vices 
… 24 
Max. 8 addresses
Number of wires 
(+3 wires for emer-
gency operation) 
26 2 2 
(+3 wires supply) 
Type of cable 
Twisted   1) 
Flat cable 
Twisted 
(Un-twisted per-
missible) 
Twisted 
(Un-twisted 
permissible) 
Twisted Twisted 
Loop line 
 
– 
 
– –  – 
T-branch 
– – 
– 
– 
 
– 
Short-circuit proof 
Yes 
Each user con-
nected with line 
separator 
– 
Yes 
Each user con-
nected with line 
separator 
No No  Yes 
Network structure 
Master/master Master/slave Master/slave 
Master/slave Master/slave  Master/slave 
Scanning 
Event-controlled, 
presence monitoring 
Cyclic, 
Event controlled 
Cyclic 
- typ. all 64s 
- Interrupt on 
alarm 
– 
Event-controlled, 
presence moni-
toring 
(All 60s) 
Cyclic 
- typ. all 250ms 
Principle 
Serial Bus 
- Cerberus protocol 
- Collision detection 
- Manchester coding 
 C-Bus 
- Cerberus protocol
- SPI/Motorola 
Sensor/actor-Bus 
- Cerberus proto-
col 'K31' 
- Serial 8bit 
- Start-up: daisy-
chain 
 Conventional 
- Current gain 
principle 
- Voltage levels 
 Network 
- Echelon Chip 
(LON protocol) 
- Cerberus 
specific telegram 
Serial bus 
- Cerberus proto-
col 
Calibrated according to cable impedance: 50Ω (MICC) / 110Ω (G51, ø 
0.8mm, not shielded) 
6.2 
Modifying the impedance of the various C-Bus cables 
 
C-Bus standard cables have a characteristic impedance of 110Ω. The driver and 
end-of-line resistors are soldered to solder lugs and can be adapted accordingly 
with other characteristic impedances (see diagram chapter 6.2.1)
1. Explanation 
A cable must be terminated with resistors. The resistance value must correspond 
to the impedance of the cable. Each C-Bus user has four end-of-line resistors 
(Ri)
. In addition two driver resistors (Rd) are integrated on the p.c.b. In order that 
the resistors can be exchanged easily they are all soldered to solder lugs. 
 
C-Bus p.c.b. 
Ri 
Rd 
B3Q700 
R31 ... R34 
R49, R50 
E3H020 
R173, R174, R177, R178 
R180, R183 
 
The driver resistors specify the current on the C-Bus. In order that the signal on the 
C-Bus always has the same amplitude (1.35Vpp), the following correlation is valid: 
Rd = Ri x 3,65 
(45Ω < Ri < 200Ω)