Bus systems 
16 
Siemens Building Technologies
 
 007836_a_en_--.doc
Fire & Security Products 
 
03.2004
 
 
6.2.1 Diagram 
 
0
0
10
20
30
40
50
60
70
80
90
100
110
120
20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440
130
140
150
160
170
180
190
200
460 480 500 520 540 560 580 600 620 640 660 680 700 720 740
Radox
Lifeline
Standard
MICC
Rd [Ohm]
Ri [Ohm]
 
2. Procedure 
 
Request characteristic impedance of the cable from manufacturer (45Ω ... 200Ω) 
 
Select the value of the Ri the same as the value of the cable characteristic im-
pedance and insert the four end-of-line resistors on the p.c.b. 
 
Insert two driver resistors Rd = Ri x 3.65 on the p.c.b. 
 
Each C-Bus user must be adapted 
If only the inductance and the capacitance are known for a cable, the impedance 
can be calculated with the aid of the following formula: 
 
Zc = 
Lc
Cc
 
Zc: 
Cable impedance [Ω] 
Lc: 
Cable inductance [µH] 
Cc: 
Cable capacitance [µF] 
 
3. Mixing of different types of cable 
In a C-Bus loop (or stub line) only one type of cable may be used. 
4. Operation as a stub line 
If the C-Bus is operated as a stub line, two end-of-line resistors (values as for Ri) 
must be inserted externally at both ends of the line (default 110Ω). In the choice of 
other cables the above rules apply (the Ri are in this case the external end-of-line 
resistors). 
 
 
For further information, see document 007831