Limitations of C-Bus participants 
21 
Siemens Building Technologies
 
 007836_a_en_--.doc
Fire & Security Products 
 
03.2004
 
 
8.1.5 Maximum 
number of I-Bus-modules 
 
Table 'Maximum number of I-Bus-modules' 
Station type 
FC700A 
I-Bus modules 
... 16     1)      ... 8    2) 3) 
1) Limited by software 
2) Value based on experience (depends on cabinet size and/or 5V current consumption) 
3) Battery charging unit E3C011 counts as one I-Bus module 
8.1.6 
Limits of 5V supply 
 
All I-Bus modules are supplied with 24V and 5V. The available current for the 5V, 
supplied from main CPU is limited: 
 
'Main CPU' 
Available current 
B3Q700 / E3C011 
250mA 
Table '5V-Current consumption of I-Bus modules' 
I-Bus module 
Current consumption 
from 'Main CPU' 
I-Bus module 
Current consumption 
from 'Main CPU' 
E3M080 55mA E3G060 10mA 
E3M111 25mA E3G070 10mA 
E3L020 10mA E3C011 12mA 
E3L030 35mA E3I020* 100mA 
E3G050 8mA  E3I040 70mA 
* Not an I-Bus module, but supplied via the 'Main CPU' 
 
8.2 
Control terminal limits (FC/FT) 
8.2.1 Limitation 
of 
visible texts on a FC700A 
 
The number of texts of other stations (i.e. AREAS) that can be displayed on one 
control terminal is limited by 14'000 texts. 
To evaluate how many control panels FC700A can be displayed to one FC700A, 
the following calculation must be used: 
 
Twice the number of visible sections (worst case 1000) 
+  The number of visible ZONES (worst case 1000) 
+  The number of visible ELEMENTS with element text (worst case 1000) 
=  Number of texts per FC/FT (worst case 4000) 
Example (worst case) 
14'000 : 4000 
(e.g.) = 3 fully configured FC can be displayed to one FC 
 
8.2.2 Limitation 
of 
visible texts on a FT700A 
 
The number of texts of other stations (FC700A) that can be displayed on one con-
trol terminal is limited by 14'000 texts. 
To evaluate how many control panels FC700A can be displayed to one FT700A, 
the following calculation must be used: 
 
Twice the number of visible sections (worst case 1000) 
+  The number of visible ZONES (worst case 1000) 
+  The number of visible ELEMENTS with element text (worst case 1000) 
=  Number of texts per FC/FT (worst case 4000) 
Example (worst case) 
30'000 : 4000 
(e.g.) = 7 fully configured FC can be displayed to one FT