Siemens FC700A User Manual

Page of 70
Specify hardware required 
23 
Siemens Building Technologies
 
 007836_a_en_--.doc
Fire & Security Products 
 
03.2004
 
 
Specify hardware required 
 
In order to be able to specify the hardware required, system key data must be 
specified according the following procedure: 
 
1. Specify number and type of detection lines 
 
Dependent on: 
– 
Detector series 
– 
Number of detectors, input and output modules 
– 
Building structure 
 
2. Specify number and type of fire control installations 
 
Dependent on: 
– 
The fire protection installations to be activated 
– 
Location of the contacts (centralized or decentralized) 
– 
Individual types of contact (250VAC/10A or 30VDC/1A) 
 
3. Specify number of operating units 
 
Dependent on: 
– 
Operating concept 
– 
Parallel indicator panels, fire department control panels 
 
4. Specify Accessories required 
 
Dependent on: 
– 
Printer interface and printer 
– 
Remote transmission equipment 
– 
Gateway, etc. 
 
5. Specify emergency power supply battery capacity 
 
Dependent on: 
– 
Total quiescent current 
– 
Required emergency current operating period (according to country) 
– 
Type of remote transmission 
 
6. Provide configuration sheet/sheets (see chapter 29) 
 
Dependent on: 
– 
Select sheets corresponding to the configuration 
– 
Complete everything