Siemens FC700A User Manual

Page of 70
Control modules 
43 
Siemens Building Technologies
 
 007836_a_en_--.doc
Fire & Security Products 
 
03.2004
 
 
17.7  Mimic Display panel outputs 
 
B3Q700 (FT)
Z3I530
24V
Data bus 
max.1000m
(Adapter)
24V
F12A100
or
F12A470
Parallel branching permissible
(not monitored)
Mimic Display panel
1
48
cable length 1m, 24 red LEDs
LED flat cable F50F410
1
48
Mimic Display panel
cable length 1m, 24 red LEDs
B3Q700 (FC/FT)
LED flat cable F50F410
LED flat cable F50F410
LED flat cable F50F410
K3R
072
K3R072
 
 
 
 
Details see document 007831 
K3R072: 
– 
Short circuit-protected outputs 
– 
Output for local buzzer and LED operation 
– 
Inputs for button 'buzzer switch-off' und 'lamp test' 
– 
Only suitable for the activation of LEDs 
– 
Outputs can only be allocated the statuses from one logical node 
– 
Max. 24 devices however max. 8 addresses 
max. permissible length
of the data bus 1000m
Key 'Lamp test'
Key 'Switch-off buzzer'
Buzzer
LED 1....24
Short-circuit proof in-/outputs
only for  
housing application
inside 
These in-/outputs can be in
parallel with other K3R072
if located in same cabinet
wires 49+50 for 'LED  operation'
LED 25....48
wires 49+50 unused
Z3I520
Synoptic display
panel housing
B3Q700
K3R072
K3R072
 
17.8 Modules 
 
 
Component Order-No.  Description 
Notes 
K3R072 
528605 
Mimic Display activation 
 
Z3I520 
484969 
Cable set for K3R072 
Comprises 12 cables (2-wire with connector, length=0.5m)
F50F410 
529141 
LED flat cable for K3R072 
50-wire, 24 red LEDs, cable length 1m 
Z3I530 
484972 
Adapter 
To adapt flat cable to terminals 
F12A100 
495275 
Flat cable Micro 12-pin, 0.4m 
From B3Q700 (FT) to K3R072/B3R051 
F12A470 
495288 
Flat cable Micro 12-pin, 1.5m 
From B3Q700 (FT) to K3R072/B3R051