18 LON-Bus 
devices 
18.1 Features 
 
 
Activation via local communication Bus 'LON' 
 
4 different types of device available 
– 
B3Q580 
Text display terminal 
– 
B3Q590/595  = 
Text control terminal 
– 
K3I050 
LON/Mimic Display converter 
– 
K3I110 
LON I/O card 
 
Connection via I-Bus/LON module E3I040 (converter between I-Bus and LON-
Bus) 
 
The function 'LON-Bus' is possible once per station type 'FC' and 'FT' 
 
Max. 32 devices per LON-Bus (device type can be mixed as required) 
 
Monitored two-wire-Bus without loop line function 
 
All devices require a separate feed line from E3I040 
 
Wiring of the LON-Bus 
– 
As 'stub line' up to 1000m (without T-branches) 
– 
As 'free topology' up to 500m (length of line to all devices added) with 'MICC' 
as 'stub line'.... 700m / as 'free topology'... 300m 
– 
With special cable (Belden 85102 or 8471) and as 'stub line' up to 2700m 
– 
Only possible via twisted line (10 turns per meter) 
 
CPU-overlapping functions possible 
 
B3Q59x: bottom three LEDs are pluggable. Allows application with different LED 
colour 
18.2  LON-Bus as stub line 
 
E3I040
Z3I1050
24VDC
FC/FT
B3Q700
I-Bus
K3I050
B3Q580
B3Q590/
595
LON-Bus
E3I040
K3I110
(not monitored)
Data bus
K3R072
or
B3R051
K3R072
or
B3R051
max. length of LON-Bus  1000m
E3I040
Z1B070
24VDC
Z1K030
 
 
 
Details K3R072 see page 43 
 