Hampton Direct H200 User Manual

Page of 32
Hampton H200 Cast Freestanding Woodstove
8
INSTALLATION
Residential Installation “C” Vent  (Single Wall)
 
Unit (with Heat Shield) 
       From Unit                           From          
From Flue Center-Line                   
 
 
 
 
 
          Corner                    
 
 
 
    A 
        B 
           C 
               D                     E 
           F
 
 
H200 
                                        17" (431 mm)   15" (381 mm) 13" (330 mm)    29" (737 mm)  17-1/8"(435 mm)      19-7/8" (505mm)
  Residential  Close Clearance (To be installed with required pipe components)
  When the stove is installed as a close clearance residential unit, a listed double wall connector is required from the stove collar to the ceiling   
   level.
 
Unit (with Heat Shield) 
       From Unit                            From            
   From Flue Center-Line                 
 
 
 
 
 
           Corner                         
 
 
 
          B 
               C                    D 
    E 
            F
   
 H200 
                                         15" (381 mm)   10" (254 mm) 9" (228 mm)     27" (686 mm)    12-1/8" (308 mm)   15-7/8" (403mm) 
Mobile Home Close Clearance (To be installed with required pipe components)
"C" Vent single wall pipe is not approved for Mobile Home installations (refer to Mobile Home Instructions).   
 
Unit (with Heat Shield) 
       From Unit                              From           
     From Flue Center-Line 
 
 
 
 
 
                                Corner                        
 
 
 
           B 
                  C 
       E 
                  F
 
H200                                               15" (381mm)      10" (254 mm)      9" (228mm)      27" (686mm)     12-1/8" (308mm)    15-7/8" (381mm)
 
 
 
 
 
 
                      
MINIMUM CLEARANCE TO 
COMBUSTIBLE MATERIALS
Please read the section below carefully. Measurements "From Unit" are from the top plate of the stove to a side wall or to a corner, and from the 
rear heat shield to a back wall.
Clearances may only be reduced by means approved by the regulatory authority.