Emerson FTA1100 User Manual

Page of 21
Use                 arrows to enable or disable this setting.  Press            to confi rm.
SETTINGS
PRESSURE
OVERPRESSURE ALARM
1
Use                 arrows to enable or disable the overpressure alarm feature.  Press           to confi rm.
Limit
Use               arrows to set the pressure limit for the overpressure alarm.   Press            to confi rm.
SETTINGS
PRESSURE
RECORDING - DELTA
1
Use                 arrows to set pressure delta recording limit.  Press           to confi rm.
HOURLY
Use               arrows to enable or disable hourly pressure recording.   Press            to confi rm.
Note: Pressure will be recorded whenever pressure changes by more than set limit.
Note: Pressure will be recorded every hour, on the hour.
SETTINGS
PRESSURE
CALIBRATION - SET TO ZERO
2
Use                 arrows to set zero calibration value.  Press           to confi rm.
SET TO SPAN
Use               arrows to set span calibration value.   Press            to confi rm.
NOTE: Remove interlock jumper wire from terminal #15 & 16 when calibration is complete.
NOTE:  Before proceeding, place jumper wire between fi eld terminals #15 & 16 to prevent starting of the engine.  A 
calibrated pressure gauge will be required to correctly adjust the settings.
Remove/relieve system pressure from the controller sensing line.  If gauge shows 0 psi, no adjustments are required; 
otherwise set zero calibration to same value as displayed on pressure gauge.  (Example: With system pressure removed 
the gauge reads 3 psi, set zero calibration value to 3).
Using calibrated gauge, restore pressure to controller sensing line.  Adjust span setting to match the value shown on 
the gauge.
Settings - Engine & Cranking
SETTINGS
ENGINE & CRANKING
CONTROL
Current value is shown (Mechanical or Electronic).  This setting determines the type of Engine being used.
RESET TO DEFAULT
Use               arrows to enable reset.   Press            to confi rm.
NOTE: Calibration setting will reset to factory defaults and reset function will automatically return to disabled.
3
Use               arrows to select engine type.   Press            to confi rm.
SETTINGS
ENGINE & CRANKING
OVERSPEED (Engine Terminal #1)
1
This setting determines if the Fuel Valve Relay (Terminal #1) remains energized during an overspeed condition.  This 
output is required on some engines.
Use               arrows to enable or disable this setting.   Press            to confi rm.
Settings - Alarm Limits
SETTINGS
ALARM LIMITS
OVERPRESSURE ALARM ENABLED
1
LIMIT
Use                 arrows to set pressure limit at which the alarm is activated.  Press            to confi rm.
SETTINGS
ALARM LIMITS
Indicates controller battery voltage setting.  Informational only - setting cannot be changed from this menu.
Use                 arrows to set minimum voltage point for Battery Trouble alarm.  Press            to confi rm.
SETTINGS
ALARM LIMITS
1
MIN
10
SETTINGS
PRESSURE
SENSOR
The maximum operating pressure of the sensor (transducer) is displayed.  Value cannot be changed from this location.
Also shown on this screen are the cranking cycle values (# Crank Attempts, Duration of a Crank Cycle, Duration of a 
Rest Cycle).  This is informational only and cannot be changed.