Emerson FTA1100 User Manual

Page of 21
SETTINGS
FEATURE SETTINGS
MANUAL TEST
1
DURATION
Use                 arrows to set the minimum run time (duration) when manual test push-button is used (10 - 99 min.).  
Press            to confi rm.
SETTINGS
FEATURE SETTINGS
PUMP RUN ALARM
1
AUDIBLE
Use                 arrows to enable or disable the audible alarm for Pump Run.  Press            to confi rm.
1
COMMON ALARM
Use                 arrows to enable or disable the common alarm output (ALR relay) for Pump Run.  
Press            to confi rm.
1
PUMP ROOM
12
Use                 arrows to select the alarm output relay for Pump Run (Disabled, PTR (Pump Room Trouble), ETR (Engine 
Trouble), Both PTR and ETR).  Press            to confi rm.
SETTINGS
FEATURE SETTINGS
REMOTE START
1
USE ON DELAY
Use                 arrows to enable or disable the on delay timer function when remote start is used.  Press            to confi rm.
NOTE: The on delay timer must be set in the TIMER SETTINGS menu.
1
AUTO SHUTDOWN
Use                 arrows to enable or disable the automatic shutdown feature when remote start is used.
NOTE: If enabled, the minimum run timer set in TIMER SETTINGS will be used.  
Press            to confi rm.
SETTINGS
FEATURE SETTINGS
USER INPUT
1
ENABLE
Use                 arrows to enable or disable the user defi ned alarm.  Press            to confi rm.
1
ON DELAY
Use                 arrows to select an on delay time before the alarm is acknowledged (0-99 seconds).  
Press            to confi rm.
1
AUDIBLE
Use                 arrows to select if the user input activates the audible alarm.  Press            to confi rm.
1
COMMON ALARM
Use                 arrows to select if the user input activates the common alarm output (ALR Relay).  Press           to confi rm.
1
PUMP ROOM
Use                 arrows to select if the user input activates the alarm output  (Disabled, PTR (Pump Room Trouble), ETR 
(Engine Trouble), Both PTR and ETR).  Press            to confi rm.
1
ON MESSAGE TEXT
Use                             arrows to program the message that is displayed and recorded when the user defi ned alarm is acti-
vated.  Press            to confi rm.
1
OFF MESSAGE TEXT
Use                             arrows to program the message that is displayed and recorded when the user defi ned alarm is deacti-
vated.  Press            to confi rm.
SETTINGS
FEATURE SETTINGS
WEEKLY TEST SETUP
1
ENABLE
Use                 arrows to disable or defi ne the frequency of the Weekly Test feature (Disabled, Every Week, Every 2 Weeks, 
...........Every 5 Weeks).  Press            to confi rm.
1
ON
Use                 arrows to choose the day of the week that the Weekly Test is performed.  Press            to confi rm.