AC International Lenze V0100 User Manual

Page of 38
ENGLISH
22
Commissioning
4.5.3 
Advanced Setup Parameters
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
Speed at 
Minimum Signal
0.0
-999.0 
{Hz} 
000
f   
P161 
P160  
ref
10V
(20mA)
0V
(4mA)
   V0
Speed at 
Maximum Signal
0.0
-999.0 
{Hz} 
000
Note
•  P0 sets the output frequency at 0% analog input
•  P sets the output frequency at 00% analog input
•  P0 or P < 0.0 Hz:  For scaling purposes only; does not indicate 
opposite direction!
•  P0 > P: Drive will react inversely to analog input signal 
Analog Input 
Filter
0.0
0.00 
{s} 
0.00
Adjusts the filter on the analog inputs 
(TB-5 and TB-25)  to reduce the effect 
of signal noise
TB-25 Loss 
Action
0
0  No Action
•  Selects the reaction to a loss of the 
4-20 mA signal at TB-25. 
•  Signal is considered lost if it falls 
below 2 mA
•  Digital outputs can also indicate a 
loss of 4-20 mA signal; see P40, 
P42
  Fault 
2  Go to Preset when TB-25 is:
  Speed reference:  P7
  PID feedback source:  P7
  PID setpoint reference:  P2
  Torque reference:  P
Carrier 
Frequency

0  4 kHz
•  As carrier frequency is increased, 
motor noise is decreased
•  Observe derating in Section 2.2
•  Automatic shift to 4 kHz at 20% 
load
   kHz
2  8 kHz
  0 kHz
()
Base Frequency
0.0
0.0 
{Hz} 
500
  
V02
Fixed Boost
0.0 
{%} 
0.0
Note
•  P7 = rated motor frequency for standard applications
•  P8 default setting depends on drive rating
Accel Boost
0.0
0.0 
{%} 
20.0
Accel Boost is only active during 
acceleration
() Any changes to this parameter will not take effect until the drive is stopped