Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
Slip 
Compensation
0.0
0.0 
{%} 
0.0
Increase P70 until the motor speed no 
longer changes between no load and 
full load conditions.
()
Current Limit
200
0 
{%} 
CLim
max
•  When the limit is reached, the 
drive displays  , and either the 
acceleration time increases or the 
output frequency decreases.
•  Digital outputs can also indicate 
when the limit is reached; see P40, 
P42.
•  Refer to section 2.2 for CLim
max
DC Brake 
Voltage
0.0
0.0 
{%} 
0.0
Setting is a percent of the nominal DC 
bus voltage.
DC Brake Time
0.0
0.0 
{s} 
999.9
Note
CONFIRM MOTOR SUITABILITY FOR USE WITH DC BRAKING
DC Brake voltage (P74) is applied for the time specified by P75 with the 
following exceptions:
•  If P=,  and P75=999.9 the brake voltage will be applied 
continuously until a run or fault condition occurs.
•  If P0=2, 4… and P75=999.9, brake voltage will be applied for 5s
•  If P2…P2=8 and the corresponding TB- input is CLOSED,  
brake voltage will be applied until the TB- input is OPENED or a fault 
condition occurs.
Display 
Frequency 
Multiplier
0.00
0.00 
 
50.00
•  Allows frequency display to be 
scaled
•  P78 = 0.00:  Scaling disabled
•  P78 > 0.00:  Display = Actual 
Frequency X P78
Example:  If P78 = 29.7 and actual frequency = 0 Hz, 
Drive displays 750 (rpm)
Run Screen 
Display
0
0     {Parameter Number} 
599 •  0 = Normal Run Screen, this display 
depends on mode of operation.  
See Section 4.2.
•  Other selections choose a diagnostic 
parameter to display (P50…P599).
Skip frequency 
0.0
0.0 
{Hz} 
500
•  Drive will not run in the defined skip 
range; used to skip over frequencies 
that cause mechanical vibration
•  P8 and P82 define the start of 
the skip ranges
•  P84 > 0 defines the bandwidth of 
both ranges.
Skip frequency 2
0.0
0.0 
{Hz} 
500
Skip frequency 
bandwidth
0.0
0.0 
{Hz} 
0.0
Note
Bandwidth (Hz) = f
s
 (Hz) + P84 (Hz)          f
s
 = P8 or P82
Example:  P8 = 8 Hz and P84 = 4 Hz; skip range is from 8 to 22 Hz
() Any changes to this parameter will not take effect until the drive is stopped