On a typical system with a current-loop amplifier and PMAC's default servo update time (~440 
sec), an 
Ixx31 value of 2000 to 3000 will provide a critically damped step response. 
If the servo update time is changed, Ixx31 must be changed proportionately in the opposite direction to 
keep the same damping effect.  For instance, if the servo update time is cut in half, from 440 
sec to 220 
sec, Ixx31 must be doubled to keep the same effect. 
This parameter is usually set initially using the Tuning utility in the PMAC Executive Program.  It may be 
changed on the fly at any time to create types of adaptive control. 
Ixx31 is not used if Iyy00/50 for the motor has been set to 1 to enable the Extended Servo Algorithm 
(ESA) for the motor. 
Ixx32  Motor xx PID Velocity Feedforward Gain 
Range:   
-8,388,608 - 8,388,607 
Units:   
(Ixx30*Ixx08)/2
26
 16-bit output bits / (counts/servo update) 
Default: 
1280 
Ixx32 adds an amount to the control output proportional to the desired velocity of Motor xx.  It is 
intended to reduce tracking error due to the damping introduced by Ixx31, analog tachometer feedback, or 
physical damping effects. 
If the motor is driving a current-loop (torque) amplifier, Ixx32 will usually be equal to (or slightly greater 
than) Ixx31 to minimize tracking error.  If the motor is driving a velocity-loop amplifier, Ixx32 will 
typically be substantially greater than Ixx31 to minimize tracking error. 
If the servo update time is changed, Ixx32 must be changed proportionately in the opposite direction to 
keep the same effect.  For instance, if the servo update time is cut in half, from 440 
sec to 220 
sec, 
Ixx32 must be doubled to keep the same effect. 
This parameter is usually set initially using the Tuning utility in the PMAC Executive Program.  It may be 
changed on the fly at any time to create types of adaptive control. 
Ixx32 is not used if Iyy00/50 for the motor has been set to 1 to enable the Extended Servo Algorithm 
(ESA) for the motor. 
Ixx33  Motor xx PID Integral Gain 
Range:   
0 - 8,388,607 
Units:  (Ixx30*Ixx08)/2
42
 16-bit output bits / (counts*servo update) 
Default: 
1280 
Ixx33 adds an amount to the control output proportional to the time integral of the position error for 
Motor xx.  The magnitude of this integrated error is limited by Ixx63.  With Ixx63 at a value of zero, the 
contribution of the integrator to the output is zero, regardless of the value of Ixx33. 
No further errors are added to the integrator if the output saturates (if output equals Ixx69), and, if 
Ixx34=1, when a move is being commanded (when desired velocity is not zero).  In both of these cases, 
the contribution of the integrator to the output remains constant. 
If the servo update time is changed, Ixx33 must be changed proportionately in the same direction to keep 
the same effect.  For instance, if the servo update time is cut in half, from 440 
sec to 220 
sec, Ixx33 
must be cut in half to keep the same effect. 
This parameter is usually set initially using the Tuning utility in the PMAC Executive Program.  It may be 
changed on the fly at any time to create types of adaptive control. 
Ixx33 is not used if Iyy00/50 for the motor has been set to 1 to enable the Extended Servo Algorithm 
(ESA) for the motor.