Turbo PMAC Global I-Variables 
 113 
Ixx34  Motor xx PID Integration Mode 
Range:   
0 - 1 
Units:   
none 
Default: 
Ixx34 controls when the position-error integrator is turned on.  If it is 1, position error integration is 
performed only when Motor xx is not commanding a move (when desired velocity is zero).  If it is 0, 
position error integration is performed all the time. 
If Ixx34 is 1, it is the input to the integrator that is turned off during a commanded move, which means 
the output control effort of the integrator is kept constant during this period (but is generally not zero).  
This same action takes place whenever the total control output saturates at the Ixx69 value. 
This parameter is usually set initially using the Tuning utility in the PMAC Executive Program.  When 
performing the feedforward tuning part of that utility, it is important to set Ixx34 to 1 so the dynamic 
behavior of the system may be observed without integrator action.  Ixx34 may be changed on the fly at 
any time to create types of adaptive control. 
Ixx34 is not used if Iyy00/50 for the motor has been set to 1 to enable the Extended Servo Algorithm 
(ESA) for the motor. 
Ixx35  Motor xx PID Acceleration Feedforward Gain 
Range:   
-8,388,608 - 8,388,607 
Units:   
(Ixx30*Ixx08)/2
26
 16-bit output bits / (counts/servo update
2
Default: 
Ixx35 adds an amount to the control output proportional to the desired acceleration for Motor xx.  It is 
intended to reduce tracking error due to inertial lag. 
If the servo update time is changed, Ixx35 must be changed by the inverse square to keep the same effect.  
For instance, if the servo update time is cut in half, from 440 
sec to 220 
sec, Ixx35 must be quadrupled 
to keep the same effect. 
This parameter is usually set initially using the Tuning utility in the PMAC Executive Program.  It may be 
changed on the fly at any time to create types of adaptive control. 
Ixx35 is not used if Iyy00/50 for the motor has been set to 1 to enable the Extended Servo Algorithm 
(ESA) for the motor. 
Ixx36  Motor xx PID Notch Filter Coefficient N1 
Range:   
-2.0 - 2.0 
Units:   
none (unit-less z-transform coefficient) 
Default: 
0.0 
Ixx36, along with Ixx37-Ixx39, is part of the second-order notch filter for Motor xx, whose main purpose 
is to damp out a resonant mode in the motor/load dynamics.  This filter can also be used as a low-pass 
filter and a velocity-loop integrator.  This parameter can be set according to instructions in the Servo 
Loop Features section of the manual. 
The notch filter parameters Ixx36-Ixx39 are 24-bit variables, with 1 sign bit, 1 integer bit, and 22 
fractional bits, providing a range of -2.0 to +2.0. 
The equation for the notch filter is: 
2
z
2
D
1
z
1
D
1
2
z
2
N
1
z
1
N
1
)
z
(
F
 
This parameter is usually set initially using the Tuning utility in the PMAC Executive Program.  It may be 
changed on the fly at any time to create types of adaptive control.