Hall Effect Phasing: Yaskawa Incremental encoders 
Hall-effect  sensors  can  be  used  for  rough  phasing  on  power-up  without  the  need  for  a  phasing  search 
move. This initial phasing provides reasonable torque. With a hall sensors’ error of about ±30° resulting a 
loss in torque of about 15%, it will need to be corrected for top operation. 
Hall-effect  sensors  usually  map  out  6  zones  of  60°  electrical  each.  In  terms  of  Turbo  PMAC’s 
commutation cycle, the boundaries should be at 180°, -120°, -60°, 0°, 60°, and 120°. 
 
Zone 
Definitions 
Zone 
Definitions 
 
 
#define Phase30Deg  1 
#define Phase90Deg  5 
#define Phase150Deg 4 
#define Phase210Deg 6 
#define Phase270Deg 2 
#define Phase330Deg 3 
 
#define Phase30Deg  4 
#define Phase90Deg  6 
#define Phase150Deg 2 
#define Phase210Deg 3 
#define Phase270Deg 1 
#define Phase330Deg 5 
 
#define Phase30Deg  2 
#define Phase90Deg  3 
#define Phase150Deg 1 
#define Phase210Deg 5  
#define Phase270Deg 4 
#define Phase330Deg 6 
 
#define Phase30Deg  5 
#define Phase90Deg  4 
#define Phase150Deg 6 
#define Phase210Deg 2 
#define Phase270Deg 3 
#define Phase330Deg 1 
 
#define Phase30Deg  3 
#define Phase90Deg  1 
#define Phase150Deg 5 
#define Phase210Deg 4 
#define Phase270Deg 6 
#define Phase330Deg 2 
 
#define Phase30Deg  6 
#define Phase90Deg  2 
#define Phase150Deg 3 
#define Phase210Deg 1 
#define Phase270Deg 5 
#define Phase330Deg 4 
  
In order to decide which set of definitions to use for a motor, a one-time test needs to be done. It consists 
of  forcing/locking  the  motor  to  a  phase  with  a  current  offset  and  reading  the  state  output  of  the  hall 
sensors. 
 
  Record the values of Ixx29, and Ixx79 to restore them at the end of test 
  Set Ixx29=0, write a positive value to Ixx79 and issue a #nO0. 500 is a reasonable value for 
Ixx79 to start with. Increment as necessary to force the motor to tightly lock onto a phase. 
  Record the Yaskawa Incremental Sensors Data. The result is an integer number between 1 and 6 
(a value of 0 or 7 is not valid) representing the zone of which definitions to be used in the 
subsequent PLC. Remember, Turbo PMAC allows only nibble based register definitions, so in 
order to read bits 1 thru 3, a 1-bit right shift or division by 2 is necessary: