Delta Tau GEO BRICK LV User Manual

Page of 271
Geo Brick LV User Manual
 
Troubleshooting 
 250 
D1: Error Codes 
 
The  Geo  Brick  LV  utilizes  a  scrolling  single-digit  7-segment  display  to  exhibit  amplifier 
faults. In normal operation mode (logic and DC bus power applied), the Geo Brick LV will 
display a solid dot indicating that the software and hardware are running normally. 
 
 
 
DISPLAY 
DESCRIPTION 
 
Solid Dot: 
Normal mode operation. No fault (s) 
GLOBAL FAULTS
 
 
Under Voltage: 
Indicates that the bus voltage is not present or less than 12Volts 
 
Over Voltage: 
Indicates that the bus voltage has exceeded 85Volts 
 
Over Temperature:  
Indicates that the (internal) electronics have exceeded 65°C 
AXIS n FAULT (n = 1 through 8) 
n
 
Axis n Over load: 
Indicates that channel n ‘s current rating (0.75A / 3A / 15A) has been exceeded 
n
 
 
Axis n Over Current:  
Indicates that channel n ‘s peak current has exceeded the permissible limit (20 A) 
 
 
Note 
In  order  to  reset  (clear)  the  amplifier  faults  through  software,  the 
power-on PLC (which specifies the motor types, clears error bits, and 
activates the strobe word write-protect) must be enabled.