STANDARD VS. WINDOW MODE 
The terms “Standard” and “Window” describe two methods for 
setting up the Smart-Switch
TM
 to monitor pressure. 
Standard Mode 
In Standard Mode, illustrated in Figure 8, the SP1i (or SP2i) set 
point actuates when the pressure being monitored goes above the 
set value. At this point, the Smart-Switch
TM
 might turn off 
whatever electrical power is being applied to a pump, for 
example, which is increasing or maintaining the pressure. The 
switch de-actuates, or resets, when the pressure drops below the 
preset decreasing set point (SP1d or SP2d). At this time, the 
electrical power to the pump would be turned back on. 
 
Figure 8   Standard Mode 
INCREASING SET POINT
DECREASING SET POINT
DEADBAND
SWITCH
DEACTUATES
SWITCH
ACTUATES