Deadband 
The deadband is the separation between the increasing set point 
and the decreasing set point, as shown in Figure 8. The deadband 
can be anywhere from 1% to 99% of Full-Scale Output (F.S.O.). 
In the case above where the Smart-Switch
TM
 is controlling a 
pump, a wider deadband reduces the frequency at which the pump 
cycles on and off. 
Window Mode 
This mode is useful when you want to maintain pressure within a 
certain range, and want to be notified when pressure either goes 
above or falls below that range. In Window Mode, the Smart-
Switch® starts out actuated, then deactuates when it reaches its 
lower set-point (SP1d or SP2d). As pressure continues to 
increase, the switch actuates again when it reaches the upper 
set-point (SP1i or SP2i). This range between the lower and upper 
set-points is the "window". When pressure decreases, the 
sequence reverses, with a deadband of 1% of F.S.O. at each of the 
set-points. See Figure 9. 
In this mode, the Smart Switch
TM
 might be wired to, say, an alarm 
bell, which would sound if the pressure either rose above SP1i or 
fell below SP1d.
 
 
Figure 9 Window Mode 
WINDOW
UPPER BOUNDARY
(INCREASING SET POINT)
LOWER BOUNDARY
(DECREASING SET POINT)
NO = OPEN
NO = CLOSED
NO = CLOSED